Can we use droop CT in neutral in place of W phase of
alternator ?
Answers were Sorted based on User's Feedback
The droop CT can be placed anywhere in the W phase. In
series star connected alternator it can be placed in the
output end, centre tap or neutral (star point end of the W
phase winding).
Remember it must be inserted as per the instructions as to
how many parallel coils pass through it and P1 must always
be in the correct direction. Always have P1 towards the
star point.
I have done this a number of times where the room around
the windings do not allow fitting elsewhere.
| Is This Answer Correct ? | 0 Yes | 0 No |
trasnfarmaer core make
How to calculate capacitor bank value to maintain unity power factor with some suitable example?
If an electrical component has a positive temperature coefficient, how come such components have high power losses due to heat if current decreases when resistance increases? assuming power given by I^2*R whereby the Resistance is infinite.
what do u understand from filter factor of reactor?
how to define tell me about self
what is ratio test?
why power factor occur only inductive load not in resistive ?
Why field resistance is greater than the armature resistance in dc mechine
1 Answers Cape Peninsula University of Technology,
what happens if generator is running leading power facotor?
11 kv input, 66 kv input advantages
what is high tension ? specify the range?
In a synchronous motor. if start is running at high speed. What will be the starting torque : Higher Lower Zero
Civil Engineering (5086)
Mechanical Engineering (4456)
Electrical Engineering (16639)
Electronics Communications (3918)
Chemical Engineering (1095)
Aeronautical Engineering (239)
Bio Engineering (96)
Metallurgy (361)
Industrial Engineering (259)
Instrumentation (3014)
Automobile Engineering (332)
Mechatronics Engineering (97)
Marine Engineering (124)
Power Plant Engineering (172)
Textile Engineering (575)
Production Engineering (25)
Satellite Systems Engineering (106)
Engineering AllOther (1379)