Off Load Tap changer generator Step-up Transformer, My
question is, is safe to operate the tap say I want to
change the tap position from 3 to 4, there is not load on
the transformer but a 22000v 0r 1100 v is present on the
secondary side from the common Bus *22000V/415 v
Answer / chaitanya
off load tap changer is not only on no load on transformer
but transformer should be de-enrgised condition i.e.
voltage on supply side should be cut-off. This is due to
off-load tap changer is not designed to change the tap when
on voltage energisation.
| Is This Answer Correct ? | 4 Yes | 0 No |
What are the requirements of a good organization?
why comparable interface is marker interface in java?
dear friends, pls tell me why silicone oil is used as dielectic medium in pressure transmitters
I m doing my B.tech in production engg.... can i apply for the company? In which subjects i will have to focus for the preparation?
how could you change gas line control valve to liquid line valve?
what is the need of rectifier?
formula for convert liter in to pale
CHMER EDM MACHINE PRINTED CIRCUIT BOARD
what is Automated smoke test suit? and why we use thah in QTP??
pls sir can any body tell me the important questions of power plat operatoe my id is ali.ind85@yahoo.com plss
what is bearing and how manytype of bearing
reversing of each word in the string
Civil Engineering (5086)
Mechanical Engineering (4456)
Electrical Engineering (16639)
Electronics Communications (3918)
Chemical Engineering (1095)
Aeronautical Engineering (239)
Bio Engineering (96)
Metallurgy (361)
Industrial Engineering (259)
Instrumentation (3014)
Automobile Engineering (332)
Mechatronics Engineering (97)
Marine Engineering (124)
Power Plant Engineering (172)
Textile Engineering (575)
Production Engineering (25)
Satellite Systems Engineering (106)
Engineering AllOther (1379)