Off Load Tap changer generator Step-up Transformer, My
question is, is safe to operate the tap say I want to
change the tap position from 3 to 4, there is not load on
the transformer but a 22000v 0r 1100 v is present on the
secondary side from the common Bus *22000V/415 v
Answer Posted / chaitanya
off load tap changer is not only on no load on transformer
but transformer should be de-enrgised condition i.e.
voltage on supply side should be cut-off. This is due to
off-load tap changer is not designed to change the tap when
on voltage energisation.
| Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
what is impeller clearance?
Dear friends, I got admit in one of the u.s university.I didnt take TOEFL and the university which i had applied have accepted IELTS instead of TOEFL.But i am worried whether the u.s visa interviewers will accept IELTS.please tell me your views about this problem and also suggest how to answer this question.If anyone had faced the same problem please E-mail and share your experience to me.I would be gratefull if you do me this help. Thankyou
Define operation time?
what does EN230 material mean?
pls sir can any body tell me the important questions of power plat operatoe my id is ali.ind85@yahoo.com plss
EXPLAIN WHY YOU CONSIDER YOURSELF SUITED FOR THIS POSITION:
why data registers are needed in PLC ?
What are the requirements of a good organization?
What points should be kept in mind to build an effective organization?
How improvements can be made for designing the parts?
What is process analysis?
What is quality management system? Weather qms is suitable, adequate and effective or not? Is there any quality policy? Is there any quality objective? If yes, then what are they? How they are planning to achieve quality objectives? Do they are measure quality objectives?
what is fixed bearing?
axial displacements of the turbine. What could be the causes?♪ ♪
What is difference between npn & pnp sensors?