Off Load Tap changer generator Step-up Transformer, My
question is, is safe to operate the tap say I want to
change the tap position from 3 to 4, there is not load on
the transformer but a 22000v 0r 1100 v is present on the
secondary side from the common Bus *22000V/415 v
Answer Posted / chaitanya
off load tap changer is not only on no load on transformer
but transformer should be de-enrgised condition i.e.
voltage on supply side should be cut-off. This is due to
off-load tap changer is not designed to change the tap when
on voltage energisation.
Is This Answer Correct ? | 4 Yes | 0 No |
Post New Answer View All Answers
what is alternater & engine genral protection?
What you know about ISO 9001? What is quality management system? Weather QMS is suitable,adequate and effective or not? Is there any Quality Policy? Is there any Quality Objectieve? If yes, then what are they. How they are planning to achieve Quality objectives? Weather they are measuring quality objectives?
what is load capacity of 11 cm cylinder bor 100kg. pressor?
can you give me the solution of iiie
why data registers are needed in PLC ?
what is a benifit to configure site to site vpn ?
whats te normal transformer current rating
Which two groups of management manages the control organization and what are their responsibilities?
Can any One Help me to Know about Fire hydrant and its related water Pressures
What kind of tools and materials are required to test water softening system of heating plant?
How important are statistics in industrial engineering?
ANY ONE USED/INTERFACED CITECT VERSION 6.0/1 OR 7.0/1 TO SIEMENS S7-300 OR S7-400 CONTROLLER IF PLEASE TELL ME THE COMMUNICATION STRUCTURE AND ADDRESS CONSIDERATION FOR DI,DO,AI,AO please mail the details lok_pallapolu@yahoo.com Ph:09247513753 hyderabad
what are the different ripple removing circuit . which one is better and why
What is fauit level
what is fixed bearing?