Off Load Tap changer generator Step-up Transformer, My
question is, is safe to operate the tap say I want to
change the tap position from 3 to 4, there is not load on
the transformer but a 22000v 0r 1100 v is present on the
secondary side from the common Bus *22000V/415 v
Answer / chaitanya
off load tap changer is not only on no load on transformer
but transformer should be de-enrgised condition i.e.
voltage on supply side should be cut-off. This is due to
off-load tap changer is not designed to change the tap when
on voltage energisation.
| Is This Answer Correct ? | 4 Yes | 0 No |
Can any One Help me to Know about Fire hydrant and its related water Pressures
What kind of tools and materials are required to test water softening system of heating plant?
what is the standard time in production management ?
CHMER EDM MACHINE PRINTED CIRCUIT BOARD
which MRP type is suitable for spare part
what is the need of rectifier?
what is machine tpm
What are the areas where I need to make improvement? (Please provide examples and suggestions for improvement).
hoe to calculate Multi grade sand filter diameter,size and media qty. ?
What points should be kept in mind to build an effective organization?
What is plant organization?
What environmental controls?
Civil Engineering (5086)
Mechanical Engineering (4456)
Electrical Engineering (16639)
Electronics Communications (3918)
Chemical Engineering (1095)
Aeronautical Engineering (239)
Bio Engineering (96)
Metallurgy (361)
Industrial Engineering (259)
Instrumentation (3014)
Automobile Engineering (332)
Mechatronics Engineering (97)
Marine Engineering (124)
Power Plant Engineering (172)
Textile Engineering (575)
Production Engineering (25)
Satellite Systems Engineering (106)
Engineering AllOther (1379)