Answers / { k.prakashchandra }

Question { Jindal Steel and Power, 4075 }

What is the function of mid point voltage in battery bank


Answer

Midpoint is taken as +/ - 0 potential . It is usually earthed through a high resistance . It can be used for DC earth fault indicator and to check the presence of any polarity

Is This Answer Correct ?    1 Yes 0 No

Question { Integral BioSciences, 1971 }

Why 1500 rpm of deasel generator please explain to me?


Answer

50 Hz , 4 pole

Is This Answer Correct ?    1 Yes 0 No


Question { OCL, 2306 }

If a capacitor bank is having rating 750kvar for 6.6kv. Then for 3.3kv how much will be the rating of capacitor bank.


Answer

Voltage is halved and also the current drawn by the capacitor bank. The rating will be 750/4 kvar

Is This Answer Correct ?    0 Yes 0 No

Question { TATA, 2400 }

why breaker closing coil gets burnt if supply is continously provided to it.


Answer

It is short time rated ,say about 5 seconds max .

Is This Answer Correct ?    1 Yes 2 No

Question { Private, 2155 }

During the main stator winding insulation testing (phase to ground)of 11kv alternator (Lerysomer) i found 0 and resistance with multimeter and found 20 killo ohm while the power cables are connected both end (Generator & VCB). In VCB PT (Potential transformer) are connected.
Please any body explain that method of insulation is correct or not? also describe of PT connections


Answer

Supposing that you have disconnected the neutral of GEN , you will measure the dc resistance of PT as the other end of it is earthed . 20 K ohm will be measured as 0 M ohm by the megger . If you want to test insulation of GEN , you have to isolate the winding from everything .

Is This Answer Correct ?    0 Yes 0 No

Question { cpgn, 2225 }

Why reverse relay used


Answer

It is reverse power relay i.e . directional wower relay

Is This Answer Correct ?    0 Yes 0 No

Question { 2765 }

I have 10 amp MCB for my air conditioner of 1.5 ton capacity. When I connect the ac direct it is started running but when connected through stabliser the Mcb Get trip and air conditioner couldn't start.please confirm whether Mcb is required to be upgraded to 20 amp. There is no fault in ac and the stabliser. Please advice the reason of tripping the mcb when connected through the stabliser.


Answer

The initial in-rush current is about 3-4 times the normal current when there is stabilizer as it consists of a transformer . If you keep the switch of the MCB pressed with your finger for a short time while switching on the AC ,the MCB may not trip. You can go in for a 30A MCB

Is This Answer Correct ?    0 Yes 3 No

Question { Trimax, 4871 }

what is RR number Abbreviation energy meter


Answer

Mostly , Revenue Reference number

Is This Answer Correct ?    0 Yes 0 No

Question { 1568 }

i need to calculate high voltage line power factor daily basics but there is meter reading kwh and kvah
while calculating power factor kwh/kvah formula was right. for examble there is point c=13kwh c=1.8 lag c=1.2 lead and c=14.5kvah
like that i know that p.f =kwh/kvah
but c=1.8lag kvarh and c=1.2lead kvarh
points i dont know

if u know please reply


Answer

The average pf is 13/14.5

Is This Answer Correct ?    1 Yes 0 No

Question { Adhunik, 3147 }

how starting current in motor is reduced in case of motor in star connection.


Answer

The motors are usually designed to run in delta connection i.e. each of the three windings to take line voltage . When you start in star connection , each winding is subjected to phase voltage , Hence the starting current will be less .

Is This Answer Correct ?    0 Yes 1 No

Question { Shree Lingaa Polymer, 2044 }

Hi,

I'm running plastic reprocessing company where all motors are running only in delta. Due to that when I use start my 30 hp motor my transformer gets fuse. Where it happens two times a day. I gt a suggestion from a person about Automatic Power Factor Controller APFC. Is it useful for my problem??? Or is der any other way for solving this problem?? Upgrading the transformer is difficult. Pls give Me ur suggestion. Waiting for ur reply.


Answer

Check the continuous rating of the fuses

Is This Answer Correct ?    0 Yes 0 No

Question { 2412 }

Which type of alternator used in power station?


Answer

Synchronous generator

Is This Answer Correct ?    2 Yes 0 No

Question { 2057 }

How to select the ratio of neutral ct? Is there any relation in between percentage impedance and neutral ct ratio ?


Answer

It should be equal to that of line CTs ,with same magnetic characteristics if you are employing REFR

Is This Answer Correct ?    1 Yes 0 No

Question { 1887 }

Why neutral has to switch on-off with phase in TN IT TT systems i.e neutral should be taken as fourth pole


Answer

As a safety measure , the tr is completely isolated

Is This Answer Correct ?    1 Yes 0 No

Question { Electrical, 2000 }

Calculation for the adequacy of 380 KVA neutral earth flat size


Answer

Neutral earthing wire should be at least capable of taking the full load current continuously

Is This Answer Correct ?    2 Yes 0 No