what are the problems are there
if power factor is leading
Answer Posted / sk arman
When the power factor is leading, the capacitive kVAr is
more than the Inductive kVAr and this still has to be
supplied by the source. As kVA is the vector sum of kW and
kVAr, still for the given kW, you have to produce more kVA.
Alternately, for the given kVA, you can only convert
partially into useful work.
Secondary effects are voltage boost in the system,
availability of stored energy to feed the fault in case of a
fault, increase in the asymmetrical component of fault
current, increasing thus the peak value of the fault
current, etc.
| Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
How to calculate mf when meter equipment and meter are connected
Inverter. converter. Ups.MCB.solar.alternators. motors.
Explain about how is it working Earth fault'relay and wahts the resistance value of earth bed
how to select the no. of brushes in a lap winding?
what is the chiller and working principal
How to find out damper winding failure for synchronous machine?
which VFD is better ( LT or HT)
what is the affect of earth's magnetic field on the frequency used in aircraft???
How to select a transformer group to connect a 0,433 KV generation with 33 KV grid in bi directional flow of current
How relay coordination has to be done? what are the inputs are required for this? Please explain this with calculation method?
why ht motors are star connected?
how does this job compare with others you have aplied for?
Will any motor burn if voltage provided is lesser than the rated voltage???? If yes, then how is speed control possible with voltage control
What is the actual calculation for transformer short circuit test?.
1600 KVA ka transformer hi aghar lt side par 800A aur voltage 420 ho to HT side ki cable ki rating keya ho gi?