if 50hz transformer is required to be run on 50% frequency
what needs to be done???????????
Answer Posted / pankaj rajput
It will trip on over fluxing protection, if the protection
is installed.
It's not a wise situation to connect transformer to a lower
frequency with same voltage. The flux induced in core is
directly proportional to voltage & inversly proportional to
frequency. Hence the core will be over heated/over fluxed
and may get damage due to over heat.
The only remedy is reducing the voltage in same ratio.
Is This Answer Correct ? | 31 Yes | 2 No |
Post New Answer View All Answers
Some times to change of DOR of a motor, interchange of R & B is not effected and RYB take same current, but interchange of R&Y is effected ie change the DOR. My doubt is what is the problem in motor and how it is happen.
what are the accessories need to be added while doing estimation for the following: 1.MCCB 2.MCB 3.ACB
ho can we calculate the conductor insulation value according to their ratings like voltage,current etc.how insulation value related with voltage,current and power of amachine
what is calculation mathod/formaulla for deciding Size of busbar (Copper/ aluminum)for L.T. panel on Various Fault level like 50kA,25kA,10kA
What is the tipical Online UPS input voltage for 20 KVA load ( 3 Phase or 1 Phase )? Why ? Explain it...?
What will happen if the d.c. Shunt motor opened accidentally running on no-load has its shunt field winding?
how can i find ct ratio of meter by seeing name plate of meter and how it should be used in MF calculation if it shows only-/1???
description about dry type transformers
what kelvin's law ?
What’s electric traction?
why on axial hitting up of air blast on hydrogen produced in oil circuit breaker,temperature rises of the core of the arc?
how to select automotive wire by mathematical equation with given current, vlotage and resistance
What is the formuala to calculate the rating of motor protection circuit breaker
ITI r/tv trade APPLY (J.T.O VACANCEY) ALSO INCLUD AITT ELECTRONIC,WRITEEN XAM DONE 23.03.10 BUT NO RESPONCE WHY ANATHER ID gopal_gh007@rediffmail.com
Why is a plain induction motor unsuitable for wide speed control?