Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

what is pf. how to calculate capacitor bank value to
maintain unity pf.

Answer Posted / nilesh kumar singh

Power Factor is defined as the ratio of Real power and
Apparent power.

for calculating Capacitor bank value the formula is :

kVAr = KW {tan(cos^-1 Phi e) - tan(Cos^-1 Phi d)}

Where - Phi e = existing Power Factor.
Phi d = Desired Power Factor.

Is This Answer Correct ?    101 Yes 8 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why is control bus bi-directional?

2172


how we calculate the withstansing current capacity of wires&cables?

2023


what are the steps involved in generator load test?

1564


how to increase senstivity of ct

2434


How does zener phenomenon differ from avalanche breakdown?

1184


why do we carry out winding resistance test?

2298


explain supply side and demand side energy management with advantages & disadvantages

2156


An active element is one which a. Supplies energy b. Absorbs energy c. Supplies energy and convert energy from one form to another

2079


a)In a 3-phase 4-wire circuit, a circuit breaker is selected to protect the circuit whose highest fault level is 6.6 MVA. Determine the required minimum breaking capacity in kA. (Note: Covert 3-phase power in terms of kA to find answer.) b)Using the below, determine the required minimum making capacity in kA as a “peak value”. Rate breaking capacity (Icn) ka: Icn<= 1.5 Factor = 1.41 1.5

1712


Discribe type of fault in DOL and stardelta startor.

2242


When steam condenses and becomes water at the same temperature, the specific heat for the process in kJ/kg k is

1145


what is the safety of voltage power transformer(2250KVA0

1990


What is power factor why we should maintain the power factor unless what will happen

1925


How to derive detailed design of Suitable bus Bar for 100A for 6.6KV?

1820


how to design the heater in temperature control unit to heat 50KL of water?

1930