1 ton AC takes how much current( starting & stable)
Answer Posted / tony
All the answers are actually wrong. MCBs can handle quite a larger current (2-15 times, depending on type) for short period of time so you don't consider inrush current.
Type B: 3-5 times
Type C: 5-10 times
Type D: 10-20 times
The breaker in the distribution box usually is dependent wire gauges. You can adjust the mcb with socket according to load.
Use type C for ac. Only use 1.5 times of the running current. I use 13A for 1.5 ton ac.
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
what is under coal gassification?
Is the installation of the filter cloths necessary before spreading the gravels at the transformer yards?
why we use single core 630mm2 cable for transformer secondary side
What is meant by vector group
internally connection of photvoltic module
Dear sir, How to calculate 3.5 core pvc aluminium armoured cable meter wise carrying amps rating.Please give the solution with a good example.
Why armature rheostat is kept in maximum position?
i karmveer bharti persuing b.tech . plz send me syllabus and name of reference books. for preparation of section eng.
what is interpose? where it is used and why it is used?
HOW TO CALCULATE EARTHING SIZING?
What is the procedure/activities to be taken to inject the current more than 2000A by using 2000A Loading Transformer?
we have a rewind motor of 2Hp,2800Rpm, 220Volt AC. how can we choose the running capacitor for this motor, any formula for that?
What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.
how to calculate transformer load?
dear all i am kumara now current working in electrical designing of control and relay panel i want learn some substaion design then any book are available. pls mention name and authour