how to claculate earth strip size for 1500kVA transformer
for neutral and body

Answer Posted / chandan tripathy

As per IS 3043, Cross Section Area of Earthing Conductor
(A) =(If x√t) / K
Where:
t = Fault current Time (Second).
K = Material Constant.
Example: Calculate Cross Section Area of GI Earthing Conductor for System has 50KA Fault Current for 1 second. Corrosion will be 1.0 % Per Year and No of Year for Replacement is 20 Years.
Cross Section Area of Earthing Conductor (A) =(If x√t) / K
Here:
If = 50000 Amp
T = 1 Second
K = 80 (Material Constant, For GI=80, copper K=205, Aluminium K=126).
• Cross Section Area of Earthing Conductor (A) = (50000×1)/80
• Cross Section Area of GI Earthing Conductor (A) = 625 Sq.mm
• Allowance for Corrosion = 1.0 % Per Year & Number of Year before replacement say = 20 Years
• Total allowance = 20 x 1.0% = 20%
• Safety factor = 1.5
• Required Earthing Conductor size = Cross sectional area x Total allowance x Safety factor
• Required Earthing Conductor size = 1125 Sq.mm say 1200 Sq.mm
• Hence, Considered 1Nox12x100 mm GI Strip or 2Nox6 x 100 mm GI Strips

Is This Answer Correct ?    25 Yes 5 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

There is air in a room . the top and bottom of the room are at constant temp. T1 and T2. DRAW THE temp profiles if a. T1 greater than T2 b. T1 less than T2

1417


what is difference between cpp electrical system and refinery electrical system

1730


what is KA rating and how can we choose switchgears on applications

956


What is meant by positive and negative feedback?

620


Explain the process of commutation in a dc machine.

598






pls tell me function of closing coil of A.C.B.

2878


Name the types of motors used in vacuum cleaners, phonographic appliances, vending machines,refrigerators, rolling mills, lathes, power factor improvement and cranes.

680


Why we cant store an ac power. If we coo store in which device we can?

1632


state the working of discharge lamp?

1561


What is the difference between the transmission line and distribution line?

653


what is the difference b/w ATS and HTS?

1696


A Generator is in running condition and Rotor earth fault alarm is coming.How to check on line(i.e in running condition) whether there is actual earth fault in rotor or not.

1452


what is meant by star/delta voltages as 440/220 in a 3 phase induction motor, and why it should be connected on STAR IN 3 PHASE SUPPLY

1767


What is effect on in zone and out zone fault if CT chosen for phase side is Vk/2<5mA and Neutral side is Vk/2<15mA on REF protection of Transformer

1892


why sielent pole is used only in hydro generators and not in turbo generators

3346