how can we calibrate the differential pressure transmitter
by using HART communicator
Answer Posted / deepak kumar
for DPT calibration on the field :
1.at first go the field and check our tag number to which u calibrate
2.then first close the both HP & HP side isolation valve,open the equaliser valve
3.open the vent valve
(for zero triming there is pressure flow)
4.then connect the HART communicator at ve and -ve terminal
5.open the hart =>>device setup=>>diagnosis=>>calibration=>>sensor calibration =>>dp trim=>>then enter Zero trim at atmospheric pressure
(that solve)
NOTE:-after complete the calibration close it to it's normal conditions..
.
thanx...
| Is This Answer Correct ? | 7 Yes | 0 No |
Post New Answer View All Answers
What is zener diode? What is voltage regulator?
Draw a simple circuit for a well head control panel used to protect the well against fire, leak, blockage, ESD, & controls the operation of one downhole & one surface safety valve. Explain the operation and controls
Describe the functions of the Operator Interface including the considerations related to alarming and display layout/configuration/layers.
how to calibrate corollaries (Mass flow meter)?
Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell
Why is the orifice tab provided?
What is stripper & spilitter ? Diffrence in this.?
In which principles tx ,pressure gauge,Temp gauge,control valve works?
Explain the burnout feature.
Instrumentation Safe Guarding test. How to determine the interval time of the test. eg:Halfyearly,Every year,Every three years etc.
How to decrease opening & closing time of on/off valve?
what is zero and span ?
what is different between 2,3&4 wire rtd and how much maximum distance using plc to field.
what is stroke check for field instument transmetter's & AOV's
can anyone guide me how to get any of the previous year GAIL question papers? are they available? 0n 2nd august i have to take the written test.