if field commnictor 475 does not communicate with transmitter
what will you do ?

Answer Posted / abu maryam

In my opinion there are several causes of this problem:
1- Check the power source if it 24 volt or not.
You should disassemble the power source if it is 24 on out side and still 24 after connecting to device this mean that the power source is good but if it is 24 volt out side and zero after connecting this mean there is found problem in power source (may be problem in module).
2-Read device data if it support hart protocol or not.
3-Disassembled device and connect separate power source and connect 250 ohm series if it no benefit added change the resistance from 250 to 1000 ohm and try or disassemble the resistance and power source and apply power source from multi function calibrator which has internal resistance then try to connect.
4-May be device support hart but hart property is disabled by definite internal jumper in device so we should change this jumper according to device manual.
5-May the device support hart its data files is not added to hart communicator for 1 of the following 2 reasons:
the first:hart communicator is not updated.
The second:the device data filed is not added to hart communicator and it need its special programs and its special cable as found in foxporo transmitters.
6-May the connectors or cables has problem so use another cable.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

How does work A temperature valve or fv control valve in process plz brief me

1924


selection criteria of control valve? and selection criteria of actuator explain in brief?

3655


what is the reason while warning lamp is on while the engine is cranking?

1624


what different types of problems do occur while doing instrumentation commisioning and how to solve them? please explain in detail

1321


How to Calibrate Ultrasonic flow Transmitter in Field

798






Decibel.

2086


while i check zero check for dp flow transmitter some fluctuating came (0 to 458 kg/h) what is the reason?

1347


What is Alpha & Beta fctors related to Orifice Plate & its relation with flow?

2929


I was working on calibrating turbidity transmitters endress+hauser at effluent polishing plant.We calibrated using NTU buffers.What happened is that when we immersed the sensor, everytime we raise and lower the sensor gradually, the reading will vary.my question is that is there any specifications on what is the required distance from the bottom of the container with buffer to the face of the sensor?Is it ok to install the sensor in a medium which has turbulence specially if bubbles are present?

1735


dear sir we have insatlled positioner model no.sipart PS2 make Siemens at our control valves . now problem is if we want to increase the response of valve opening speedy /fast. what parameters do we change for positioner ? any idea. please guide us.

1408


CONTROL VALVE OPERATING IN MANUAL BUT NOT IN MANUAL. WHAT SHOULD BE THE PROBLEM ?

1461


Why the ammonia and Nitric Acid level indicators is with millimeter ? and What is the conversion form millimeters that level indicator indicate to weight ?

1221


What is difference between Ionization heat and bimetallic heat

1149


Why is the orifice tab provided?

713


i am from instrument branch i want paper patern of mahagenco . any pevious years paper regarding my branch send me please . please.....

1606