Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

how to calibrate motorized operated valve?

Answer Posted / subash krishnan

Instruments required:
Multimeter, potentiometer, point position trnasmitter (PPT), Valve Positioner, allen keys 3mm and 4 mm , double-end spanner (12-13), mini screw driver.

1.Initially check the motor-operated valve for open/close manually since the torque set should be accurate inorder for accurate calibration process.

2. Choose a potentiometer a desired based on the number of rounds in which the valve opens or closes. For example if the rounds are maximum choose a potentiometer which has the lowest resitance (1 kilo ohm).

3. Also choose the matching teeth wheel for the chosen potentiometer.

4. Take a point position transmitter (PPT) which is used to give the present position of the motor-operated valve. The PPT is of two different ranges based on resistance (0 to 230 ohms) & (0 to 500 ohms)

5. For every motor-operated valve the close position resistance is set as 100 ohms and the open position is set as 230 (to 500 ohms).

6. The point position transmitter is now given the power supply of 24V DC .

7. Now the resitance for the close position i.e. 100 ohms is given as input and the current should be tuned as 4mA.

8. Now the resitance for the open position i.e. 230 to 500 ohms is given as input and the current should be tuned as 20mA.

9. The steps 7 & 8 are repeated until the PPT gets set to 4 to 20mA.

10.Now the teeth wheel is matched with the matching wheel in the motor-operated valve setup so that the resistance could change in accordance with the valve's open/close operation.

11. The valve is now checked for open/close so that the current for open/close should be in the range of 4-20mA.

12. Now the positoner unit should checked whether it displays 0-100% for the open/close position. Otherwise the positioner display should be tuned for 0-100%

13. There is an actuator tuning adjustment in the positioner unit inorder to do fine calibration for zero and span if there are any minor errors in open/close position.

Is This Answer Correct ?    10 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

SOME OF YOUR QUESTIONS ARE NOT MAKING ANY SENSE SO TRY AND PUT IN A LITTLE BIT MORE EFFORT BEFORE YOU POST A QUESTION. WE WILL ONLY HELP THOSE WHO WE CAN SEE ARE TRYING TO HELP THEMSELVES.

2365


What do you know about gail?

2480


why is an oxygen sensor used in a boiler stack

7331


what can of fault ofently come in vibration mesurement?

2151


Explain Gas Turbine startup and shutdown sequences

4324


We are using Rosemount 5400 series Radar Level Transmitters in all types of Sump Applications having oily water hdrocarbon petrochemical nature. What we are facing the problem frequently is that always getting reading frezzed at some value. If we do power recycling , sometimes it is working . then making same freezing problem. If anybody faced before such type of problem and also having solution , Please give the answer.

2333


Draw a group of instruments interlocked to a Pump & Motor?

1296


what is cems analyzer explain with principle and drawing ?

2388


Explain the working of rota meter.

1224


Which Signal hart communicator work? If there any signal change when hart connect while transmitter in line ?

1412


I am using 971 Enraf radar level transmitter for LPG tanks ,the tank side indicator gives the error code 999999999FL can any body give me any diagnostic for this issue?

2208


how to work MIL contol valve posistioner ?

2148


Which are all the commonly used Bordon tubes in the pressure gauges. Do any one use ASTM A 312 tubes for this purpose?

1782


how u calibrate sox nox co2 co in cemps?what is opacity n HPm?tell the standard parameters of cems?

3673


plz tell me clearly about PID.."when v have to change I value,D value,GAIN??

2182