Answer Posted / e mohana priya
A basic liquid sizing eqtn.. is as follows:
Q = C
V
∆P / G
(1)
where:
Q
=
Capacity in gallons per minute
C
v
=
Valve sizing coefficient determined experimentally for
each style and size of valve, using water at standard
conditions as the test fluid
∆
P
=
Pressure differential in psi
G
=
Specific gravity of fluid (water at 60°F = 1.0000)
Thus, C
v
is numerically equal to the number of U.S. gallons of water at 60°F that will flow through the valve in one minute when
the pressure differential across the valve is one pound per square
inch. C
v
varies with both size and style of valve, but provides an
index for comparing liquid capacities of different valves under a
standard set of conditions.
To calculate the expected C
v
for a valve controlling water or other
liquids that behave like water, the basic liquid sizing equation
above can be re-written as follows
C
V
= Q
G
∆P
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
Calibration procedure for electro magnetic flow meter
How to calibration a control valve?
Draw a great bridge circuit.
where cascade loop use ?
Why does a pressure gauge installed on reactor, doesn't have any vent line below to release the pressure? Is it any kind of designing mistake or it actually does not require any vent line? And if it does not require any vent line below it then how we are gonna release the pressure built inside the pressure gauge?
i have steam drum height 1000mm. and i want to placed the transmitter below the tap.how i calculate.
Please asked me How calculate DCS controller memory.
What is defferent betwen ESP &PCP PUMP .HOW IT IS WORK?
how do i tune dearator pr control valve using PID. we set the set point is 0.6kg/cm2 now i want 0.5 to 0.7kg/cm2 limits so what should i give p,i,d values. then pls explain how do set pid values for control valve tuning?
What is feed factor and its Importance in cement industry? How we can solve feed factor?.
what is orfics working in main steam line. is it increase pressure, velocity of steam flow and dicrease steam flow rate. or any other
what is piezoelectric transducer?give an example in power plant n state its principle?
how does we calibrate a square root flow transmitter ,give an example and explain it step by step like range calculation , calibration hook up series connection , zero check , and how to apply pressure , and if not geting proportional output then what should we do ?
In apron feeder how TPH is calculated?
if in a level tx height is given, how u calculate the ranges of the tx?