Dear Sir,
we met a disaster with our 62.5 kva genset, after rewinding
we informed by our contract engg that due to return current
coming in neutral & impropper earthing this happend.
But after all set up & load balance we checked & found
again we have about 20 to 32 amp return current on neutral.
we have 12 airconditioner + 12 mini fridge on single phase
line.
Pl suggest any idea to solved this problem
Answer Posted / sheikh
I think imbalance load is main reason of this problem and cross current compensation instrument transformer should be installed on your common bus bar to prevent this loss
but balance load all of 3 phase eleminate the highest neutral current.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Explain the operation of variable frequency transformer?
Why field rheostat is kept in minimum position?
What are the different towers used in 132kv transmission line? what are the differences between the P,R,S towers used in 132KV and detailed explanation
how to design coil turns ?
Do Phase angle measurement have any application in freq/harmonics measurement? If so how?
How to resolve if Diesel generator stop while running ?
What is power relay?
On what basis do you decide the ONAN (Oil Natural air natural) or Dry type transformer for a project?
whats the existence of reactive power and when it arises?
What is power in wattage of 8.5 TR AC
What is Phase margin?
How to calculate multiplying factor of dc energy meter
Do any one know exacatly when the results for NHPC held on 8th march 09 for engineering trainees will be released ?. if so please post it, i'm eager to know it.
can we synchronize star system generators with delta system transmission line ? and how ?
My question is abt backlog.I had dropped one subject in my second year, and completed this subject in the 3rd attempt, so how many backlogs i have got?1 or 3?plz sujjest the answer as soon as possible