How to calculate unit consumption on the basis of load.
kWH=kwXhrs.is it correct? kw is motor load.What is unit
consumption at 100% load, 50% load & on no load.

Answer Posted / tushar amarghade

for 100% load
unit(kwh)- kw*hours/1000
where,
KW for single phase- V*I*PF
KW for THREE phase- 1.732*V*I*PF

Is This Answer Correct ?    4 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Which are resistive loads & which one are inductive loads : Refrigerator, Split air conditioner, ceiling fans, well pump, fluoresecent bulbs, T.V, CRT Monitors, Adsl Routers, C.P.U, Printers, Deep Freezers, Speakers, DVD Players, Microwave oven etc. ? Output Power for these Appliances Would be same like this : P = V * A * P.F Or would be changed ? thanks

3418


What is the ratio of Booster transformer?

1651


State the points to be considered for selecting a particular type wiring.

1626


how to electronic energy metter failed in electomagnectic fild passing in the metter and which thing to defect more on metter.

1493


What are merits & De-merits of State-Space Method? What is series programming, parallel programming, general programming & direct programming ? And, difference between these programmings Techniques ?

1935






What is mean by spike arrester(Voltage Operated)

1612


How to calculate multiplication factor in kva example 500kva ans pls ?

1381


If we have to find the inductance of a dc shunt motor then by giving dc supply or ac supply and what is the reason for it. (this example is from "to determine the transfer function of a dc shunt motor ")

1527


What are the various types of rotor used in the alternators?

618


Explain in details how you would react to an unexpected incident when your supervisor or manager is not around to give instructions?

7314


sugest any typical project ?

1374


Can we use 230VAC, 63A MCB for 120VAC, 63A supplied heaters load?

1029


What is main cause of cable's terminal point burned in Lug on high temperature although lug and cable selection is ok as per stantard and also tightness is ok as per situation. so please take in deep and tell correct answer thanku.

7387


we have 15 ampere variyac but we want 30 ampere variyac what we do

1418


how does WTI work ?

1531