if a dp transmitter has range 100 in H2O and flow is 20mmcf
and if the flow is changed to 25 mmcf then what is the
formula to determine new range of transmitter
Answer Posted / carl_ellis
design max flow rate = 20 mmcf
design max DP = 100 in H2O
new max flow rate = 25 mmcf
new max flow rate = ?
The max flow rate increases by 125% over the design max flow
rate:
25/20 = 125% increase
DP calculations are done in normalized percentages. 125% = 1.25
To calculate the corresponding DP at a max flow rate 125%
higher than the original, where X = DP
sq rt of X = 1.25 (square root of normalized percentage
of DP)
X = 1.25^2 = 1.562
1.562 = 156.2% (work in normalized percentage)
156.2% of 100 inH2O = 156.2 in H2O at a max flow rate of 25 mmcf
Carl Ellis
Measure First
Is This Answer Correct ? | 3 Yes | 0 No |
Post New Answer View All Answers
What is 1:1 redundancy ?
-/5A. What is the meaning and limitations of this in energy meter constant. It is a 3 phase LT Energy Meter. If this Energy Meter is connected through a CT of ratio 200/5 Amps, then what is the multiplying constant and how its will be calculated.
pls give me presant awerness quistion and answer in my emailid.
What is instrumentation technologists and mechanics?
How to work temperature gauge?
please send data bank of quetions answers on analytical instrumentation.
what is the usage of QDV & VOLUME BOOSTER
Type of level transmitter commnly used in Procees area are the following. a.________________This type of level transmitter works as follows
what is interface level and how it is calibrate?
what is scale factor of proximitor & unit of the vibration.
Why humidity limit is 30 to 55 % for raw material storage?
what can of fault ofently come in vibration mesurement?
What is the difference between conductive lined pipe and conductive unlined pipe? Why do we see that?
how to check earthing,what is minum ohms for proper earthing
What is the reason PT speed not incresed in gas turbine?