in short circuit. test of a
transformer 5 to 10%
ofvrated voltage is used why??? if
we use rated
voltafe then what will be?

Answer Posted / 7anoter4

The 5-10% of rated voltage represents the short-circuit
voltage that means if you connect all the secondary
terminals of the transformer together-it is a “short-
circuit”. If you supply the primary winding terminals this
short-circuit voltage you’ll get the rated current-primary
and secondary.
If the supply voltage is the rated voltage you’ll get the
short-circuit current [10-20 times the rated].

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

700KW 6.6KV slip ring induction motor to use VFD to control the speed

2784


State kirchoff voltage law?

692


What are the different losses In a de mac1une'! t.xplam

2271


33kv substation lay out details & line to line & line to earth measurements

2170


I am interested to know what does 15 KVA DG set actually means? If I dont know the DG rating, is it possible to identify KW by simply knowing the diesel consumption?

1618






I need the list of Universities who have summer intake for BS degree in Electrical Engineering.?

1568


How to measure power in 2 or 4 or n phase circuit? Please give me a formula.

1469


What is the use for cable entry in control room?

719


can we install HT panel & LT panel side by side or how much clearance is required ?

1098


what is conductor copnstant of ab cable

1331


how mass curve differs from hydrograph.

1301


Explain about Dubai electrical sysaem? Explain about Dubai drinking water system? Explain about Dubai Burj tallest building Electrical,Water.etc.. maintenance system?

1664


Why IR value of the (HT cable Plus synchronous motor) is less while individually having IR values in GΩ?

1356


how we will deside the high voltage value

1465


What will be result if we connect LT votage to the terminal of HT motor?

1721