How to calibrate level switch?
Answer Posted / aftab ahmed mazari
Suppose you using Float/ displacer type of level switch.
Do the followings:
1. Fill the process into chamber of level switching mark.
2. Contacts of level switch should be changed.
3. If already, closed contacts, then should change to open condition.
4. If contacts not changing, do the knob of switch to change.
Suppose you can not fill process into chamber.(Process may harmful, like ammonia etc).
1. Note the process specific gravity. Suppose it is 0.67.
2. Your height for level switching is 1000 mm.
3. Use water to fill into chamber for calibration instead of process.
4. 1000 x 0.67 = 670 mm
5. So fill into chamber up to 670 mm water. It will operate the switch.
aftabmazari@yahoo.com
| Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
what are the steps I have to deal with?
which type of zones used for boiler? & why ?
What are primary elements of measuring pressure? Which type of pressure can be measured by these elements?
what is the reset offset and control system in instrumentation
Is it ok, to use non-contact type Radar type LT, on a tank that is half circular from the bottom side? If yes the, isn't the waves gonna bent in other directions?
when placing a vent or drain hole on an orifice plate should you measure from the center of the bore up or down for the vent placement?
Where are oxygen analysers installed in cfbc boilers? What are their usual readings?
tell me the field & lab calibration procedure step by step with diagram of pressure gauge, pressure switch, pressure transmitter, temperature switch, level switch, flow switch, flow transmitter, temperature transmitter, temperature indicator, flow indicator, level indicator, control valve, thermocouple, pressure indicator (digital & analogue),
how to design orifice plate?what is the equation?
what is The specifications for oriface instalation
Hi, Is there any smart plant instrumentation design training institute in Bangalore?
How process line mpm calculation is done?
What are the application of bernoulli’s theorem?
How it the difference between force balance system and dispalacement balance system?
I am using 971 Enraf radar level transmitter for LPG tanks ,the tank side indicator gives the error code 999999999FL can any body give me any diagnostic for this issue?