My rtd working well at the same time r/i converter is not working properly.when power is given to rtd..it is giving 30mA and getting 2.4 mA if i remove the compensate leads No matter how many ohms.why it is happening like so?what is the solution?rtd range-0-200deg c& 4-20 mA o/p.please give me solutiin anyone......
Answer Posted / carl_ellis
Any 2 wire, loop powered 4-20mA transmitter that puts out
30mA is broken. The only transmitter that puts out 30mA is
a legacy 10-50mA transmitter from 20-30 years ago.
While the upper end of the 4-20mA signal range is 20.0mA,
most 2 wire, loop powered transmitters allow for some slight
signal over-range, typically 20.5mA.
NAMUR standards use 21.0 mA to signal a fault or failure
mode. Other vendors use other values, 20.8mA, 21.2mA or
some value in the range of 21mA. But no vendor uses 30mA
as a fault mode.
The transmitter is broken or dysfunctional.
Carl Ellis
Measure First
Is This Answer Correct ? | 5 Yes | 0 No |
Post New Answer View All Answers
Explain the difference between plc and cnc?
what is the procedure to callibrate temp controller ,pressure controller,etc. suppose a temp controller showing error 1.5 degree centigrate how can i minimize it.
How oil line flow measured?eplain about instruments used and working principle?
What are different types of orifice plates? State their uses.
What is the difference between mmwc and mmwg?
Why is it necessary to use compensation leg to measure the liquid level in a closed or pressurized tank?
What is the main difference between Cavitation and Flashing?
What is heating effect?
What are the materials available to prepare individually for competetive exams in Instrumentation field? Plz reply...
What is the GK Value in Flowmeter?
Square root calculation for dp flow transmitter?
kindly sent some demo question and answer
How does temperature bath work? How does coil gets heated only by applying some current?
why we are using drum level control valve air to close?
Coal mill Instruments Equipments for cement plant And process diagram ?