In close vessel/ drum why we use d.p. transmitter of -ve
range i.e. (-)500 to 0 mmwc.
Answer Posted / venbha123
If the LP leg of the transmitter is kept dry, steam may get condensed in the LP leg because of which the level indication may be wrong. Hence We are using wet leg for LP side of the transmitter, which is initially filled with pure water. When the drum is at zero level, the pressure difference is only the head pressure acting on the LP side - that is 100% level head at LP side. Normally in DP transmitter the HP side pressure will be more than the LP side. In this case since the pressure in the LP side is more than the pressure in HP side the range is mentioned as negative. At 100% level both the head pressures at HP & LP are the same, the DP becomes zero. Therefore the range is mentioned as: from negative value to zero.
| Is This Answer Correct ? | 12 Yes | 2 No |
Post New Answer View All Answers
Derive capacitance to 4-20ma conversion formula / relation in capacitance type pressure sensor?
Can anyone send most commonley asked Instrumentation questions and answers in cement industry please?
There are many type of control cable like pair,core,tried, What are defination each one
What is intrinsic safety mean.
what is The specifications for oriface instalation
wich is coming the first HAZOP OR SIL
Difference between dcs and plc including date processing and architecture.
Hook up resistance decade box to temp.transmitter.
Explain working principle of lvdt?
what is Best Among SINK Or SOURCE Type Design In Digital Signal, Either Iput Or Output? WHY?Can any one..
Calibration of controller (pneumatic)
What is three element in drum level?
How to decrease opening & closing time of on/off valve?
How does your previous experience relate to the job you are applying for ?
Please can anybody help for control valve sizing step by step procedure?