We in my plant one of the transformer showing neutral to
earth voltage is 22V how to solve it

Answer Posted / wasim

Check resistance of earth pit/mesh connected with Start
point (Neutral of Transformer). If reisitance is more than
5 Ohms your Neutral to earth voltage will be increased
accordingly. So you have to improve the resitance of your
earthing network to less than 1 Ohm

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are the different types of hydro schemes?

673


What is resonant frequency?

704


How harmonic block test are conducted on relays ( Siemens,Areva ect )power transformer using omicron kit?

1749


what is the Pickup/drop off ratio in BCPU relays

4158


am commissioning the trafo without connecting the neutral therefore unbalance will occur what is the alternative solution for this?

1356






How would you calculate power loss in a resistor?

628


how choose conductor&depending upon load

1434


how many types are their in switchyard or substation(like D,I TYPE), what is differant between them

1657


trasnfarmaer core make

1529


why single phase to grd test in HV cable?why not 2 phase at a time?

1813


how much GROUND & NEUTRAL VOLT maintain in data center.

1535


What will be the voltage regulation of a full load and 0.80 power factor lagging load transformer when a two winding single phase transformer has a voltage regulation of 4.5% at full load and unity power factor?

737


What happens if the Capacitive Voltage Transformer Primary neutral is not earthed. There is a CVT between Transformer and source, and the CVT neutral of the transformer is not earthed, does it effect the transformer while charging or does it effect the transformer charging process.

3534


mccb service sittings be done?

1364


what is the method of earthing of a transformer using electrodes?

1723