Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

I know during Surge Impedance Loading maximum power is
transferred through a transmission line and also Sending end
voltage becomes equal to Receiving end voltage i.e Vs=Vr so
my question is if both end voltages are equal then how
current travels in such line hence how power is transmitted
because flow of current needs Potential difference??

Answer Posted / gopal

actually here we are dealing with phasors in AC system .and
Vs and Vr are equal in magnitude but not in phase angle.
power flows from Vs/_&#7519; to Vr/_0 according to the equation of
real power flow
P= Vs Vr Sin(&#7519;) Vs/_&#7519; - Vr/_0
------ = ---------------
Xs I
actually in phasors although their magnitude is equal but
still their difference is not zero and an appriciable
voltage difference exist between the two ends which trigger
current and hence power to flow,

Is This Answer Correct ?    4 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

how to calculate

1702


what is the excess air in furnace

2057


As per standard, transformer body earthing and other Equipment earthing (Equipment earthing) did not connect. but in LT side termination we are doing metal glanding in both side Transformer to PCC Panel through armoured cable, now X'mer body earthing and PCC Pane earthing (Equipment earthing) both are connect.is this safe for X'mer or other equipment?

1779


Give the topology of current amplifier with current shunt feedback?

1223


how to find Harmonics and types as per the equipemnts

1302


how to determine the cable size...pls explain me with the formula taking particular load....does the factors like impedance & short circuit rating influence the cable size, if so how....

2067


In an ACB shunt trip coil and undervoltage coil operated normally( breaker open and charged). But closing coil not operating untill manually discharge and recharging. Any help.

1760


what the function breaker failure scheme, how is it operated

1920


We have a couple of oil tanks at our plant. One of them does not have a lightning arrester installed. My question is it necessary to install an arrestor on every tank or will this particular one be covered by the arrestor installed on the ajdacent tank, Since all the tanks are close to each other. Basically, I want to know that if these arrestors or protection works in a parituclar area of effect or influence. Thanks

2064


Graphs of measuring power and speed on dc motor

1974


We have drive feeding an output contactor for a 5000 hp motor @ 5kV application. The motor FLA is 629amps x 1.25% service factor = 786.25 amps The cable that we current have in place between the drive and the output contactor is 350kcmil- MV-105 (parallel cables). Per the NEC table 310.60 (C) (69). This show the cable ampacity is at 615 amps per cable for a rating of 1230 amps. We have derated the cable for the cable tray and the multiple cables application and our calculations show that after the correction factor factor we are at 922amps. 1230 amps x .75% correction factor factor = 922.5 amps. The customer is driving us to then use another safety factor of .25% off of the already derated cable. Can you please provide a longhand calculation for your solution on this application?

2154


How to improve fuel cell in a distribution system?

2002


What are the main parts of central chiller plant? Explain the function of each stage.

4820


how to calculate singlephase motor efficiency?

2250


how tto ingress mw in turbine explain.procedure ?

2317