Capacitor panel CT is normally fixed on Y phase of the main
panel.why???

Answer Posted / zia

Good day friends
some time some of factory's lode not same in R,Y,B.
Example R=155amp, y=140amp, b=145amp which one we selected
for apfc relay for sense observing p-f . we are selected the
maximum amp flow phase.it can be R or Y or B. for good pf
rating.
so its a CT depends on the flowing amp of the phase

Is This Answer Correct ?    3 Yes 1 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

explain which quantities change in the starting and the and the running condition in induction motor

955


What is the previous name of Cox's Bazar

1702


how to select correct size of power cable for inverter duty motor

922


How do I calculate a WTI CT ofa 1250kVA 6600/400V transformer

1311


Why we are going for converter transformers for DC drives application instead of distribution transformer?

1444






what is the differance between HT motors And LT MOTORS.

1538


Whats the minimum value for I.R. that can be allowed for HT & LT alternators for operation?

3415


If I bring a basic electric meter from the States and hook it up in Costa Rica in a development that has only one transformer for the 50 homes, will it still be accurate regarding the usage of kilowatt hours?

1497


does a DG set has low fault level as compared to that of a transformer.If yes then why.

1529


What types of question are done for diploma students in aptitude test

1083


for 100 HP Induction motor service factor is 1.2(SF) we placed a VFD at the motor side load is balance with 0.3 Amp's Phase to Phase but at incoming of VFD load is un-balance with 10 to 20 Amp's what will be cause of load un balance

1523


what shall be no load voltage of 132/33 kV transformer ? is it 33 kv of 34.5 kV

1716


can any one tell in easy method for circulating current ??

1650


What will be electrical cost per sqft for IT building (basebuild and fitout)and for residential township?

1459


15hp motor wound by 0.9mm & 0.95mm magnet wire. at no load test it draw 4.2A current. Another motor with same condition draw 9.2A current. How can that occur? pls help

1114