in GEAFOL Cast-Resin trnaformer of 11/.72kv which has
tapping of 11550v,11250,11000,10246v in primary side. To
obtain 700v. which tapping should be used of HV side as we
have 11000v/720v tapping now .
Answer Posted / 7anoter4
If the primary voltage [supplied by Utility] it is NOW 11
kV and your transformer at no-load shows 720 V at its
secondary terminals the ratio primary/secondary voltage is
11/0.72=15.278. If you want to reduce the secondary to 700
V you have to change the ratio to 11/0.7=15.714.
Let's say the rated secondary voltage [at no-load] is 720 V.
That means the ratio 11250/720=15.625 it is the most
suitable and you'll get 11000/15.625=704 V at secondary
terminal [at no-load].
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Explain the term parallel path in dc machin ?
what is mean by PIR in circuitbreaker and give me detail of that?
delta motor winding resistance I take normally single winding is 2.5, which value is came delta connection ie RY ?
What is the maximum operating temperature for a thermoplastic insulated cable?
what is the difference between switch yard to residential area.and how much required it.
why does connected a indutor with mnsformeretering core of current transformer ?
Why the power generated in dams is complex power? Why the generators in dams cannot produce Real power directly (i.e power which has zero reactive part)?
what is the difference between b c d curves on mcb
i want to know about torque of slip ring induction motor
Difference between Earthing Truck & Earthing trolly for HT panel
List few applications of d.c series motor?
We have 90mX100m hangar with 16 no.of supporting pillar. It is required to provide power supply on all pillars. what is suggested earthing scheme for hangars.
I am having a 1500 KVA transformer whose secondary current is 2086A and my connected load is 1000 KVA, I am having 400 KVAR APFCR for PF improvement what ratio of CT should i install in LT EB Bus to get optimum PF improvement?
Explain (in simple ) - root mean square. whats its role in electrical fundamandal.where its used
How much current will a 5 HP delta connected motor at no load will take?Is tat need a starter