We operate a 10 Mw facility and we have been experiencing
several trips due to fluctuations on the MVAR? We have
checked all issues related to the AVR and we have found all
OK? Can anyone help us? The grid voltage, internal voltage,
all regular parameters look ok. MVAR fluctuate and there it
goes the unit? What could be happening? Thanks!

Answer Posted / a.j.pailwan

Please check CT connections, CT Specifications and
saturation of particularly B phase as this CT feed back is
used in AVR during PF control mode while pareller with grid.

Is This Answer Correct ?    0 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why is control bus bi-directional?

1708


Why we use circular(Stepped) cross section in transformer core?

1758


why industry prefer ht motor instead of lt motor.

1649


what's the difference between abs/inc encoders. apart from the position remembrance what are all the other differences. and what's mean by grey code.

1569


i had aplied Hindustan Petroleum corporation limited for the post of maintenance technician -Electrical,i want model questions,if anybody have please send it or please advice?

1429






how to calculate percentage impedence at 75 deg C at normal tap

1798


what is Fan Control Cubicle

1886


How can we convert 11 kv to 440 volt without using transformer ?

982


how to i get B licence,i am completed BE electircal and electronics engineering.i want to konw the proceduure to get b licence

1178


What does the kvar means?

665


In Plumbing services What are accessories we consider for a bathroom?

1552


what is the meaning of vcc

1899


what questions are asked in the interview for the post of an electrical maintenance engineer in FMCG companies?

2148


How you will determine the volume of oil in a particular Distribution transformer.

1439


What kind of Neutral CT can be placed in 11/0.433KV transformer to be used and what are its specification?

1406