Answer Posted / carl_ellis
There is no national or international standard for 24Vdc in
industrial instrumentation and control.
The use of 24Vdc has evolved out of common practice and has
seen global use and acceptance as a 'de facto' convention,
as opposed to a formal standard. The acceptance goes
beyond loop powered transmitters, it goes into discrete
control as well.
The reasons are many.
1) 24Vdc is a low enough voltage to be considered 'safe'.
It is accepted as a voltage level that does not shock human
beings through contact with dry skin.
2) 24VDc is a high enough voltage to do real work with
currents that are practical.
3) An enormous array and variety of field instruments and
controls can be designed and operated intrinsically safe at
24Vdc, not just loop powered transmitters.
4) Loop powered field instruments powered by 24Vdc can
drive 500-600 ohms of load resistance, enough for one valve
positioner (split ranging 2 valve positioners with a single
current output driven by 24Vdc is difficult).
5) Lead acid batteries are useable for battery back-up or
UPS supplies.
6) On the discrete side, 24Vdc is sufficient voltage to
break through oxide coating on switch and relay contacts
7) For discrete control, 24Vdc offers a tolerance band
around binary 'high's and binary 'low's of more than a
couple volts, which allows for operation in a moderate
level of electrical noise.
8) Statistically, 24Vdc devices have failure rates about
half of that of 120/240Vac actuation devices (relays and
solenoids). This a serious consideration for emergency
shutdown or SIS systems.
Carl Ellis
Measure First
Is This Answer Correct ? | 10 Yes | 0 No |
Post New Answer View All Answers
Lux meter is the measuring device to measure the lux level of lighting fixture. in industrial sector two types of lighting fixture is being used as street lighting purpose 1. HPSV (Sodium) and 2. HPMV (Mercury). HPMV having white light which is an combination of red, blue and yellow colour, while HPSV haivng Yellow lighting. in HPSV red & blue colour will be absent. during measurement of the lux level of HPSV and HPMV fixture. 1. Lux meter can measure the actual lux level of both fixture? 2. or it will show false reading for HPSV fixture light as it has only yellow light present. please give me answer
In Safe Guarding test what means by "Failed to Danger" ?
Which is your favourite subject & explain any one topic of it.
Define the terms Accuracy, precission, Spam, process tolerance while doing calibration of an instrument? Explaini with an example?
how many maximum enter 2mm Dia solid cylindrical pipe into 8mm Dia hollow cylindrical pipe. give answer with calculation.
How can i test procedure grounding for CAT-7 cable? Or How can we test procedure CAT-7 Cable Electrically safe?
how can i check vortex shedder bar it is ok? if there is ohms condition are shown correct?
Explain why use mmwc unit?
How to calculate P,I&D value in PID controller ?
How is PH sensor works ?
Tr. Wiring for calibration.
how pressurize drum calibrated ?
How u measure the massflow in orifice flow measurement techniques
How to check vortex flow meter is in good condition while we do not having calibration setup?
What are primary elements of measuring pressure? Which type of pressure can be measured by these elements?