what are the possible reasons if a control valve fails to open/close?
Answer Posted / carl_ellis
I seen 10 to 20 causes for each of these categories, but
I've only listed one as an example.
Reasons for valve not closing or opening:
intentional or unintentional
- lack of energy - air/electric/hydraulic (Fuse blown)
- insufficient energy - (supply air regulator turned down)
- control system issue (control signal interlocked)
- positioner or I/P issue (locked in manual)
- actuator crippled (punctured diaphragm)
- positioner-to-actuator linkage/plumbing issue (tubing failed)
- actuator-to-valve linkage issue (sheared roll pin)
- valve trim damage
- foreign object blocking movement (how does all that junk
get in the piping in the first place?)
- change in design process conditions (actuator can't close
against increased line pressure)
Not all failures to actuate/move are faults - a valve could
be intentionally locked in place for safety reasons - access
to the piping/tank.
Tell 'em Carl sent you.
Is This Answer Correct ? | 15 Yes | 0 No |
Post New Answer View All Answers
Why use ball valves on Gas pipelines instead of gate & or globe valves...means basic diffrence or use of these valves..how designers knows this type of valve with rating is required...
Hi,can anyone help me out with PhD programs related to Instrumentation field?I have a degree in electronic Instrumentation?
Can anybody please let me know Orifice plate sizing calculation formula and step by step procedure
We Have Two Field bus Pressure Transmitters of Different Sensor Range (I.E One is of Lower range and Another is of Higher Range).Is same Process Line. My Question is Can i provide Saturation Limit to my field Bus Transmitter as We can provide Saturation current limit to HART Instruments. As During Low Pressure Both Working OK ,But During High Pressure, transmitter with Lower sensor range Goes to Fault mode as Beyond its Sensor Limit it can Measure, So may I provide Saturation point Some where to Suppress This Fault during High Pressure.
What is the purpose of the analyzer in petrochemical plant?
what are the selections available in configuring a burnout protection of a controller? thanks
What is voltage regulator?
In my company plc based winders are operated. one day there was a data transmission failure alarm shown on pc. as per sir instruction we have reset master plc but winders were not triped and alarm gone. so what master plc do?
Is it ok, to use non-contact type Radar type LT, on a tank that is half circular from the bottom side? If yes the, isn't the waves gonna bent in other directions?
any body who gone thru recent iocl interview.INSTRUMENTATION questions. I need.
how will you check torque value during Factory acceptance Test for control valve/ESD ON/OFF VALE how will you confirm this torque value is being correct, Which document will you be refer.
why I need valve guard and whats different between guard and positioner ??
Actual using of tube bender to bend 2 opposite 90 deg at correct measurement center to center of tubing.
what does the ratio 800-400-300-200/1-1-1-1-1 in the specification of current transformer indicates?
Draw a P& ID showing – orifice flange, plate, dp transmitter, isolation & bypass valves and tubing.