1 How to calculate dp transmitter
steam and water?
2 impulse line for liquid steam and
gas

Answer Posted / carl_ellis

The DP pressure/flow transmitter is mounted above the pipe
for gas applications (empty impulse tubing).

The DP pressure/flow transmitter is mounted below the pipe
for liquid applications (liquid filled impulse tubing)

Steam flow applications using DP pressure transmitters were
historically mounted below-the-pipe (water filled impulse
tubing, frequently with condensate/seal pots), until
Emerson/Rosemount recently discovered that within certain
temperature limits, a DP transmitter close coupled on a
coplanar manifold to an Annubar averaging pitot tube can
survive steam temperatures mounted above-the-pipe.

See this link for Emerson's white paper on steam service
installation recommendations:
http://www2.emersonprocess.com/siteadmincenter/PM%
20Rosemount%20Documents/00870-0200-4809.pdf

Carl Ellis
Measure First

Is This Answer Correct ?    2 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are the types of control valves available

1534


Why is the orifice tab provided?

714


What is ultrasonic flowmeter?

639


Tr. Wiring for calibration.

1574


what are procedure of sox-nox calibration

2442






What is the minimum rating availalbe for weld neck orifice in market?

1555


what is sliding spool valves?

1827


what is the responsibility of an instrument commissioning supervisor

2647


what happen if i increase height of displacer type LT.accuracy or sensitivity are affected.why?

2075


can u plz send me technical questions asked in SCHNEIDER ELECTRICAL technical paper?

4290


where proximity sensor installed on tank in loading arm application

1527


Explain operation of Haskel pump.

1548


Why all the drains(Gland sealing,ESV,Casing inlet etc) are directly connected to the flash tank instead of hotwell of the condensor in the power plant? My Email Id:naba02222@gmail.com

1863


define feed forward control loop with example and drawing?

2742


i have used level transmitter in starch cooking preparation tank. tank total height 2mtr.sometime LT display shows some error value when tank is fully empty and diaphragm side i already checked okay no problem in diaphragm area. field cable checked 24volt and mA shows correct value while tank empty mA is 4mA. 4mA i needed that 0% but display showing 10% or 15% percentage values are varying continously please give any good solution for me.....

999