Good Evening all.My question is - For a feed water line to
an equipment if i need to measure the flow we will use
orifice /magnetic/vortex depend on cost/spec.If i need to
measure a ''Alarm''signal and ''Interlock'' from one point
i think we can use orifice type in one location with 2
different tapping points - one for alarm and one for an
interlock to flow valve..If in case i need to have both
these signals(Alarm & interlock) from magnetic flow
meter,is it possible??will 2 seperate sensors will be
located inbuilt r we can program it ??..i thk we can have
one transmitter with these 2 signals...need to know any
technical issues are there?pls clarify

Answer Posted / carl_ellis

It seems you are using a flow meter's relay(s) to generate
alarm signals at various amplitudes: low, low/low, hi,
hi/hi.

The flow meter doesn't really use these alarm signals
itself, rather it generates the alarm signals and provides
the alarm signals to other devices, for whatever purpose,
alarm, annunciation or an interlock.

There might be a flow meter with 3 alarm relays. I don't
know. That's a shopping issue.

Most places will use a PLC, a controller or a DCS to
generate alarms from the analog flow signal.

But if your flowmeter doesn't have enough relays, then use
a "DC alarm trip" I/O module with the flow meter's 4-20mA
analog output.

The modules have an analog input and one or two relay
outputs with adjustable setpoints. There's probably a
dozen models on this page:
http://www.api-usa.com/signalconditioners_alarms.php

These I/O modules are not used "in a magmeter", they're
external I/O modules.

They place a small burden resistance in the 4-20mA circuit,
need an enclosure and AC or DC power to operate, but they
accomplish the task of providing multiple alarms at various
setpoints.

The 4-20mA signal is wired in series with the I/O module
and any other receiver devices.

Carl Ellis
Measure First

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what can of fault ofently come in vibration mesurement?

1681


Capacitance, resistance ( colour coding ), parallel & series circuits.

1744


Do you have reference list?

1433


why we take %i0.0 as input for twido plc

1666


Galvanizing.

1474






our kks tagging is crossing more than 12 character please suggest how to take tags in the DCS

1669


What is difference between ESD and PLC please Explain me clearly.

4380


Can please tell mi about SIOS, PRM, SERVER, and what is the diference between PIN LAN, PCS LAN,APC Server, and please send the Doc if possible for referance,mail id patil_amit17@yahoo.com

1456


What are the key features of a Distributed Control System? describing the various layers (sensor through to business system interfaces) as well as the hardware, software and security aspects of the DCS.

1800


Why flow/pressure transmitter before control valve?

1066


How to calibration coriolis flow meter?

1307


Why 4-20 amps is being used in instruments? Why cant we use any other range instead of 4-20 amps? Why only 4 amps is taken as lower limit and why 20 amps is taken as the higher limit?

1061


Explain how thw analog to digital converter works with the circuit diagram

2186


Good evening all I need a small favour regarding reliance paper i wanna probable sample papers(e&i) of reliance. if any of u have any idea about dis then plz mail me back.i belongs to electronics and instrumentation engg.so i need e&i papers. thanking u....

1658


Make a ladder diagram on LSL valve will close, on PSL valve will open and start the motor

1687