30 kVA and voltage 380/220VAC how to find out kA?

Answer Posted / bala

we need to know the Impedance of the TxR.Becos the Formula for Determine the KA value is
=power/ (1.732*400*% of Impedence)
For EX-
Power = 1500 KVA
Voltage = 400V
Impedance = 6%
short circuit = 1500*1000/(1.732*400*0.06)
= 36085A or 36 KA

Is This Answer Correct ?    0 Yes 2 No