A 30KW motor running at 1450 rpm draws 56A, how would you
determine if this is correct or not?
Answer Posted / divakaran a
P=1.732xVxIxP.F
30KW=1.732x415xIx0.8
I=30000/(1.732x415x0.8)
I=52.17 AMPS
sO the current drawing from the motor is 52 amps (Theoriticaly)
in practical the motor may draws more current as based on the load.
Is This Answer Correct ? | 13 Yes | 2 No |
Post New Answer View All Answers
what is metering cum synchronizing panel and how it is used?
What it the purpose of parallel phasing transfomers??
Why air circuit breaker off due to power failure?
Explain M Var? Which types of problem occurs when reactive power increase at the time of full load of plant and at the time of synchronize of plant?
What is effect of over voltage and under voltage on ACB
How will A Medium voltage circuit breaker(11 kV voltage level) operate under short circuit fault condition whether It is having short circuit release like Low voltage circuit breaker or relay should be given?
What is the transfer function?
How should i design a 1ph & 3 ph transformer. Kindly let meknow all steps and formulaes related to design from scratch.
How we calculat the NGR of 3phase Generator, Our generation voltage 11KV
whats the application of voltage regulation? and whats the voltage regulation's device?
What will happen if the d.c. Machine is operated below rated speed?
Explain the function and difference of Restricted earth fault, simple earth fault and sensitive earth fault with connection diagram.
How to check the thermocouple is correctly connected to cable for K type? (i,e positive pole is connected to non magnetic conductor and negative pole is connected to magnetic conductor)
what is automatic voltage regulator?we can control the vlotage by using fuzzy controller in matlab?why we go for fuzzy?
what is cause of static electricity? I experience shock when i touch metal equipment in a room ,furher check shows earth leakage showing 80ma at the DB near to the 400 MCCB?