What is output of Thermocouple at 25 deg c

Answer Posted / carl_ellis

Question: What is output of Thermocouple at 25 deg C?

I'd flunk all of you except B0nz0 because only B0nz0
understands thermocouple thermometry.

The answer is, you don't know because the cold junction
temperature is not specified. The question attempts to
find out if the concepts of a thermal gradient and cold
junction compensation are understood. Which is why, I
assume, the question does not specify the type thermocouple.

B0nz0 is correct; any type thermocouple sitting on a desk
at 25 deg C; hot end = 25 Deg C, cold end = 25 Deg C, will
read 0.0mV because there is no thermal gradient.

The cold junction temperature is the same as the hot end
temperature. Doesn't matter if it's a Type K or J or S.
With the same temperature at both ends, the output is 0mV.

But without specifying what the cold end temperature is, an
answer of 0mV assumes that the cold end is at 25 Deg C.
In the real world, it usually isn't.

The hot end can be at 25 Deg C with the cold end on a
terminal strip in control panel that's at 45 Deg C because
of the heat generated by the electronics in the control
panel. Then you'll read a negative voltage because the
cold end is hotter than the hot end!

The hot end can be at 25 Deg C and the cold end is
connected to handheld temperature calibrator in northern
Canada in the winter where the cold end terminal connection
might be at -30 Deg C.

In each case, it's the cold junction compensation that
corrects the temperature reading by measuring the
temperature of the cold end connection and taking that
temperature into account.

If I were to ask the question, I'd ask, "What is the output
of a thermocouple, both ends of which are at 25 deg C, and
why?". The answer to the first part is 0mV.

Tell 'em Carl sent you.

Is This Answer Correct ?    9 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Hi my friends Is any one who can assist me in knowing the typical interview questions for system engineer at General Electric pty Ltd

1640


I WANT SECURITY PAPER MILL, HOSHANGABAD TEST PAPER.KINDLY SEND TO MY MAIL ID

2297


Instrumentation symbols interpration, P& ID, Logic diagram analysis, Electrical drawing analysis.

1495


Question on maha cement

302


where are following valves are applicable to install. can any valve be installed any line. globe valve butterfly valve boll valve gate valve

1247






䑰ҕ䔈ҕ䖠ҕ䘰ҕ䛀ҕ䝐ҕ䟐ҕ䢐ҕ䥐ҕŹ

1520


Can I route 110 VDC and 24 VDC in a same Duct for our Interposing relay cabinet? IF yes or NO Please provide me IEEE Std. for the same. Please i required it on Urgent basis, i need to design IRP Cabinets and we have MCC 110VDC and Our Coil side is 24VDC, Please help as soon as possible.

1791


what is sil (safety integrity level

2206


What is instrumentation control?

652


What are the different types of thermistors used in industries? How to the operation of typical thermistor?

1329


what is different between 2,3&4 wire rtd and how much maximum distance using plc to field.

2284


Hook up resistance decade box to temp.transmitter.

1724


why we r opening HOT BYPASS valve during startup of a compressor?

1600


How signals can be taken through modbus?

690


Calibration procedure for water rotameters

1754