how i meggar value of 11kv alternator winding.and with meggar.
Answer Posted / kj
See extract from service manual for HV alternator.
A 5000V motorised megger or similar instrument should be
used. Separate the three neutral leads,
ground V and W leads and megger U to ground. Repeat for V
phase with U and W grounded and W
phase with U and V grounded. Minimum acceptable limits
after 1 minute for each phase are:
New machine 300 M
In-service machine 150 M
The insulation resistance should not be less than specified
and the polarisation index should be in the
order of 2 or greater at 20 ºC.
(PI = IR10min / IR1min)
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What are different types of control systems?
what are factors to be consider in electrical installation like load factor,diversity factor .....
How to calculate VA rating for CT or PT or Control Transformer?
Give accurate definitions for these electric terms: Inductor Inductance Inductive Induction Reactance Reactive Esam Baraka ٢١ ساعة
In a synchronous motor. if start is running at high speed. What will be the starting torque : Higher Lower Zero
List out the different frequency domain specifications?
Formulae for calculating the transmission line losses for different voltage levels
How can we calculate the KVA rating of a Distribution transformer from its core details?
which model T or pie model is prefarable in power syatem
why it is not advisable to run low rating (19KVA) DG sets in parallel for long durations even though they are provided with droop ckts (QDC)
What is quadrantal symmetry?
what do u understand about FACTS? how they are useful?
what is capacitor voltage transformer?? how it is different from potential transformer?
Apparent power is expressed as V * I(Conjugate). Why not in V * I ?
On what basis the the size of Lightning arrester for buildings are selected ?