How big (size) can the tertiary winding be in transformer?
Can we load the tertiary winding, if yes then how much we
can load it?
Answer Posted / rabramovitz
Tyically for stabilizing an oscillating neutral, about 35%
of the KVA (or VA) supplied. Yes, it can be loaded, as long
as you don't exceed the current rating for its gage (do not
exceed current which causes a temp rise at or below the
class of the transformer). The current capability (if
properly designed)will be about a third of a primary phase
current normalized to the tertiary ratio. (call it NI/3)on
a per phase basis.
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
How Calculet The UPS AH In Load
What is the selection process of breakers. Can any one please give a formulation on same?
Why is the frequency not changed during transformation of electrical energy in a transformer?
If the line voltage is reduced to 75% of its rated value then by what percentage current will reduce ?? 75% 25% 50% no change and why ?
What happens if the Capacitive Voltage Transformer Primary neutral is not earthed. There is a CVT between Transformer and source, and the CVT neutral of the transformer is not earthed, does it effect the transformer while charging or does it effect the transformer charging process.
Hi, My plant daily consumption is calculated as 3.8MWH but my supplier has sanctioned an power of 2.6MW per day. how can i equal or distinguish this two factors
How work of capacitor in dc supply...???
sir pls send the je exam - 2008 and other model question papers..
How to identify the start and end of 3phase 12 lead motor if U1, U2, etc numberings are lost or erased.
is there any lightning by passer is arranged in ship like buildings?
What is the principle of HIGH SPEED DIRECT DRIVE MOTOR ?
After doubling voltage from solar cells & use step down voltage transformer can we get high current output with low voltage.
What is real time power factor control panel(RTPFC)?
What are the common sources of energy?
I HAVE A 50A MCCB AS PER DESIGN LINE WIRE CONNECT UPWORD SIDE AND LOAD IS CONNECTED TO DOWNWARD SIDE TO THE MCCB.IF NOW ANY ONE CHANGE SUPPLY & LOAD(WISEVERSA) WHAT HAPPENS ? DOES MCCB OPERATION OR WORKING FUNCTION NORMAL IF YES THAN WHY THERE ARE MARKED LINE & LOAD ON MCCB.