How big (size) can the tertiary winding be in transformer?
Can we load the tertiary winding, if yes then how much we
can load it?
Answer Posted / rabramovitz
Tyically for stabilizing an oscillating neutral, about 35%
of the KVA (or VA) supplied. Yes, it can be loaded, as long
as you don't exceed the current rating for its gage (do not
exceed current which causes a temp rise at or below the
class of the transformer). The current capability (if
properly designed)will be about a third of a primary phase
current normalized to the tertiary ratio. (call it NI/3)on
a per phase basis.
| Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
What is the real function of reverse power relay in generator panel while syncronising?
-What shall be short circuit current of LV switchgear for a 1000 kva, 11.415kv, 3 phase tranformer with 5% reactance.
What is magneto on a gas generator. how it functions. its out put is d.c or a.c. how it can be checked for correct functioning
The loads are connected with phase and ground then why current flow as the loads ?
can anyone please help me to find the rupturing or breaking capacity in KA of circuit breaker (MCCB,VCB,ACB etc) of HT and LT side of a distribution transformer...please help with detailed step by step answer...thank you
Disadventage of cable-gland earthing if any ?
11kV capacitor bank of rating 2.4KVAR, is charged with protective relays of only over current & Earth fault &.......without Over Voltage, Under Voltage & Neutral Displacement Relay. Is it advisable??
What is the types of HT motor testing
HOW WE KNOW IN PHYSICALLY THE CONTACT SURFACE OF A VACUUM INTERRUPTER IS GOOD OR GOING TO DAMAGE IN A VCB AFTER ABOVE 500 TIMES OPERATED.
What is the Surge for 1.1 Phase Induction Motor(For Eg.1Hp) 2.3 Phase Induction Motor(For Eg.1Hp) 3.AirConditioner(For Eg 1Ton) 4.Refrigerator(For Eg 180Ltr or 160kW) 5.Induction Cooker 4. Ceiling Fan
what's the simultenous maximum demand (SMD)..what the diffrent MD and SMD?
HI....HOW CAN BE MESARED THE VALVE OF NEUTRAL GROUND RESISTOR WHIC IS LOCATED AT SWICHGEAR ON GENERATOR SIDE....
fuel-air ratio in a petrol engine fitted with suction carburettor,operating with dirty air filter as compared to clean filter will be
what are your career plans upon completion of the programme and the relevance of recity generation to your professional development?
Earth has zero potential then what would be the neutral potential ?