This is about the recent problem that we have faced in our
project site.
We have 6/7.5 MVA. 66/11kV three phase star - star power
transformer. The neutral was solidly connected to the
earthing mat. But because of high resistance of earthing
mat (130 ohm on LV and 180 ohm on HV), one day LV side
neutral earthing conductor melted and we had a huge damage.

Can any one plz tell me what might happen when we connect
power transformer neutral to the earthing mat which has
high resistance (>100 ohm ) ?????

Answer Posted / k.prakashchandra

Have you measured IR properly, as the values are very high
?The IR should not exceed 2 ohms for a 66 KV MUSS .I do not
know whether primary neutral is to be earthed in case of
star/star tr.It is stated that LV side IR is 130 ohms ,and
hence the maximum earth fault current will be 50A.For 7.5
MVA tr the rated LV line current is about 400 A and EFR is
likely to be set at 80A.It appears that the earth wire
melted due to continuous earth fault current.If there is
conductor to ground fault at a distance of 100 m from tr
earthing ,there will be a pd of 63.5 V /m along the line
between the fault point and the neutral earth. If anybody
stands barefooted with feet 1 m apart along this line, he is
likely to be electrocuted as the power line does not
trip.Further the ground around the earthing also may be at
nearly phase voltage during earth fault

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the best thing to protect the motor from running over full current. CT or O/L or pressure transducer at the given pressure rating

1030


Why the moulded plug comes with domestic appliances instead of assembled plug like anchor, Vinay 5/15 A.

1572


what are the industrail measures to over ferranti effect? how would the ferranti effect the power system if those remedial mearsure arent taken? how often does this effect occurs in real power system?

1682


Importance of fault current in power transformers and how to monitor the same? How is it different from winding temperature?

1333


What is inrush current? how can calculateit? what is the affect of it?

1545






what happen ehen synchronisation is done at below rated speed

1613


standard earthing rating for power line..

1673


what size steel armoured cable is required to support 1500kva capacity. would 70mm squared be enough or would I need 90 or 120mm squared 3c plus earth

993


I need HT sphere gap calibration table. Can any body help me.

1527


Explain the term parallel path in dc machin ?

1764


How to calculate the fuel consumption for 600kva DG genset which connecting with 25%load?

1705


What is the breaking capacity of transformer and how can we calculate the breaking capacity of tranformer

1254


Why 1/3 is used in symmetrical components?

1388


Explain about how is it working Earth fault'relay and wahts the resistance value of earth bed

1032


What will happen if the voltage in my house drops from 220V to any lower voltage?

1663