Golgappa.net | Golgappa.org | BagIndia.net | BodyIndia.Com | CabIndia.net | CarsBikes.net | CarsBikes.org | CashIndia.net | ConsumerIndia.net | CookingIndia.net | DataIndia.net | DealIndia.net | EmailIndia.net | FirstTablet.com | FirstTourist.com | ForsaleIndia.net | IndiaBody.Com | IndiaCab.net | IndiaCash.net | IndiaModel.net | KidForum.net | OfficeIndia.net | PaysIndia.com | RestaurantIndia.net | RestaurantsIndia.net | SaleForum.net | SellForum.net | SoldIndia.com | StarIndia.net | TomatoCab.com | TomatoCabs.com | TownIndia.com
Interested to Buy Any Domain ? << Click Here >> for more details...

How can we calculate ngr resistance for a generator and
Transformer ?
What type of transformer requires ngr ?

Answer Posted / a s bhandari

Ohmic value of neutral grounding resister for a transformer is calculated as follows:

R = Vph/ I where I - value of fault current to be limited to flow through the neutral path, normally it is 50A for 5 sec.

Based on above, for 6.6 kv star side of a transformer
resister value shall be 76.21ohm.

Is This Answer Correct ?    0 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the function of electron gun assembly used in crt?

1197


why transformer tank is in rectangular shape what happen when it is in step shape

1465


The specific heats of the gas at constant pressure and constant volume are respectively 1.0 kJ/kg K and 0.72 kJ/kg K; the value of R for the gas is

1147


WHAT IS IM (INDEX OF MOUNTING )IN MOTORS

2048


What is the capacity of the Fastners 12mm?

2461


how external lighting design? please give examples?

1918


If there are two transformer having rating of 2.5mva, 6.6kv/440v(satr-star),and the load is 600kw then what is better to maintain less losses in transformer having both transformer in parellel or only single transformer connected to load? Please give calculated answer

2722


what clearance required for 4.5 mva dry type transformer?

2039


i have some screw comprressor with 630kw power,i have established them with simple star to delta circuit,by the way there is so much inertia when the screw comprressors start, can you offer me contactors power with 400vac or any cataluge to choose the contactors

1869


How to choose the vector group for the step up and step down transformers??? Tell me the which vector group is suitable for step up and step down transformers and whats the reason to choose and whats the benefits???

2291


plese send me the oces/dgfs sylabus and previous year question pattern of electrical engg.?

2316


Pl. give me checklist for installation & commissioning of machine tool.

2321


Difference between control junction box (cjb) and power junction box(pjb)?

4353


Which motor will you choose which can operate in both lagging as well as leading power factors?

1168


Why does inductive loads consume KVARs?

2091