In Transformer testing at Shop test we normally test for
vector group, open ckt.,short ckt. but what are the other
test performed for transformer once it reaches at site.For
e.g:if the transformer is dry having rating 1000KVA?
Answer Posted / guest
1. Insulation Resistance Measurement
a . For LT systems, use only 500V or 1000V Megger
b. For MV & HV systems, use 2500V or 5000V Megger
c. Remove Earth from Transformer neutral
2. Winding Resistance Measurement
R-N AND r-n
Y-N y-n
B-N b-n
3. Magnetic Current Test
Applied Voltage : RY YB BR
Measured Current : R Y B
4. Magnetic Balance Test
5. Vector Group Confirmation.
6 . Short Circuit Test and Differential Stability.
7 . REF Stability Test
8. Cooler Circuits.
9. Auxilliary Protection Circuits
Is This Answer Correct ? | 2 Yes | 0 No |
Post New Answer View All Answers
Dear Sir/Madam, I have one questions we have three steam turbines and one Gas turbine and our industry linked with the public network, we have protection system one of the protection is reverse power we can export just four MW only i would like to ask about how to calculate the reverse power. Thank you in advance best regards
Inverter. converter. Ups.MCB.solar.alternators. motors.
If rotor works in clock wise what happens
What id difference between power and energy?
What are test signals and their significance?
What are the advantages of hydropower?
can i connect REF and Differencial relay in 1 CT core for transformer protection?
List examples of voltage source?
what are the sample questions asking to the test cunducting for electrical superwising lisence test?
Can i replace Earth leakage relay to the faulty Earth Faulty Relay
How to assume answer to electrical questions
What are merits & De-merits of State-Space Method? What is series programming, parallel programming, general programming & direct programming ? And, difference between these programmings Techniques ?
can we use ZNyn11 transformer instead of Dyn11 transformer in distribution for effectively eliminating harmonics from the industrial loads.
what happens if dc supply is given and the remedies for it.
what are the things that can cause a three phase motor to crawl?