my company total load is 1000kw, 415volt, all load are
inductive load. incoming powerfactor is .8. we want to
have0.95 pf connecting capacitors. so now how much rating of
capacitors we have to connect? show how?
Answer Posted / rman
currently, the load is 0.75MVAR operating at 0.8pf. to enhance it to 0.95pf, the MVAR must be decreased to 0.329MVAR.
Q=0.75-0.329=0.36MVAR
0.36MVAR must be your operating reactive power. therefore your capacitance must be {0.36M/[0.36M/(415*0.95*sqrt(3))]^2*sqrt(3)} which will be your reactance at 0.0969 per phase. also to find the capacitor to be inserted per phase,assuming your frequency is 60Hz, C=(2*pi*60*0.0969)^(-1)
therefore the C=27.37mF
Is This Answer Correct ? | 0 Yes | 0 No |
Post New Answer View All Answers
how to calculate voltage drop and followed by cable calculation?is there avail in formula?
3 phase Motor will be given 2 phase after 2 to 5 second we given 3rd phase so Motor Run sum-time in forward or sum time run reverse direction. All time phase sequence is not change. Why motor run in reverse direction? Please Explain........
What are the basic components of the feedback control system?
Why an ac systems are preferred over dc systems?
In a 3 phase 4-wire system. For a 3.5 core cable if all loads are single phase and balanced, what will be neutral current? will it be sum of all phase currents? Or it will be zero? And if loads are unbalanced what will be neutral current?
PLEASE INFORM ABOUT THE IDEAL TEST RESULTS OF MAGNETIC BALANCE TEST OF TRANSFORMER 33/11 kv DELTA-STAR T/F
Differentiate between magnetic field and magnetic flux?
Whether amorphous core transformer is commercialized or not:Name of company making amorphous core transformer and what are different rating?
Why an ac solenoid valve attract the plunger even though we interchanges the terminal? Will the poles changes?
What are the different circuits in thermal power plant?
hai friends i have BSNL JTO exam on next month so if any body have model question paper or give preparation tips to my mail id kumar4486@yahoo.co.in this will helpfull for my future .plz & thank u by kumar
1)what is the function of a frequency inverter? 2)If a few frequency inverter are connected onto a device network,what are the two setting that will ensure the frequency inverter work properly on the network. 3)whats is the name of the input sensor for weigher? 4)How to confirm that the load cellis faulty? 5)Describe briefly the steps to validate that the weigher is working properly? 6)Describe the procedure to validate the flowmeter accuracy? 7)Describe briefly the steps to validate that the tempreture sensor/transformer is working properly. 8)what is the adjustment that need to be done when you are calibrating the temperature transmitter ? 9)what are the safety measures to be taken before disconnecting motor for rewinding. 10)whats is the synchronous speed in rpm of typical 4pole 50hz motor? 11)whats is the formula for kw, ohm's law 12)if a 3phase motor is rated 3kw,415vac,what is it's rated ampere?
what is the minimum clearance between a 11KV 150KVAR capacitor cell and series reactor.can a series reactor can be mounted in the same structure of the capacitor cells structure
how to find the multiplication factor for digital energy meter and analog energy meter
How do we calculate the Out put voltage of generator, after the excitation is being given?