If Solenoidal valve works in manual mode but not in Auto
mode. What should be the problem?
Answer Posted / raffi
Signal(Soft PB) for SOV to open in Manual and Auto are same (DO)
While your are running in AUTO. it is working with interlock/logic i.e feedback from other IOs
While in Manual mode you should press the SOV button to open after change the mode to manual
If it not working in AUTO then Check the malfunction of feedback signal IO card or carryout the loop checking for feedback signal to sort out the issue
| Is This Answer Correct ? | 8 Yes | 0 No |
Post New Answer View All Answers
Can combine control system for Emergency control system (ESD)and Fire & Gas System ( F & G) is possble to built and offer to client? Can such system is as per Norms in India?
What is voltage regulator?
Can anyone send most commonley asked Instrumentation questions and answers in cement industry please?
State four different types of flow measurement, for gas flow measurement MMSCFD is the common unit expand the unit and specify significance of word S in the unit.
I want to measure and control level in tank of size 10*5 filled with gasoline, so plz give me the solution with clear details. how to select transmitter and sensors.
a flow transmitter [range-0-400mbar] connected in process line. please explain me how to calibrate the flow transmitter , & how to do static error
diff between neutral ,ground,phase , earthing and shielding?
What are different type of instrument cable
How flow can be measured with dp?
how to calibrate mass flow meter (Coriolis)? Example calibration range: 0 to 2500 kg/hr line size 3" fluid: Etheline glycol (MEG)
If fire would be inside the plant which fire detector is to detected the fire.
control panel design guidelines
what are the use of belew gear in general ??
1)How many tpes of vibration probe and how many tpyes of vibration. 2)how we can calibrate a vibration probe with tk3 3)what is RMS value in vibration measuring application and how we calculate it.
what is o2 analyzer and how it measured ,what is the role of this analyzer in cfbc boiler...