Answer Posted / antaratara ghosh
assuming the load as motor,operating voltage as 415 V,pf
as .85, efficiency as .95,
rated current, Ir= (644)/(1.732*0.415*0.85*0.95)
= 1110 A (approx)
now considering VFD starting for the motor,
starting current, Ist= 2*Ir
= 2220 A
considering margin of 20%, maximum current flowing =
2220*1.2 = 2664 A
Since MCCB are not used above 630 A in India, you have to
go for 3150 A (which is just greater than 2664 A and
available in market) ACB...
Is This Answer Correct ? | 2 Yes | 2 No |
Post New Answer View All Answers
HOW CAN I GET 5CORE HO7 CABLE SIZE IF I HAVE 1800A?
Where servomechanism is used?
Define step response?
anyone knows service engineer in chennai for EDM SPARKING MACHINE.CHMER PULSE CD 60 M.pL GIVE ANY CONTACT NOS
What willbe change in programming when we use 5/3 solenoid inplace of 5/2 in operating of a cylinder?
WHY IL=IPH IN STAR AND WHY IPH=IL/1.732 IN DELTA? WHAT IS REASON BEHIND IT?
If 22 KV HT line, Current transformer is 25/5 then how to calculate multiplying factor.
what is fault level of power system ?
how to failure indution motor insulation & how to improve heat in motor insulation
Is it possible to implement Restricted Earth Fault protection for a transformer without neutral CT?
How to Make relay co ordination chart for a Electrical power distribution of a plant
at what rate the micro controller increment its timer....is it 1micro seconds or 1/(12*10^6) seconds
what is the relation between knowing of the distance between power transformer and the capacitor feeder in case of parallel operation
why d.c produces corrosion
why sielent pole is used only in hydro generators and not in turbo generators