our company have 750 kva oil transformer.still we have
facing a problem that is when voltage is 11.5 kv coming
from HT side then LT-side voltage is 420v or above at tape
1.please give me best solution to decrease the voltage

Answer Posted / sudhakar lanka

my friend, you r looking for reduce the output voltage from 420 volts,
case1: try to keep the primary tap position on maximum voltage
for example ur receiving 11.5kv , if in your transformer there is a tap voltage which is more than these value i.e 11.6kv or else apply 11.5kv on that tap position.
same as above u can try on secondary side also
case2: if u have done all the these exercise, then when u connected to load on transformer there will be voltage drop
check at that time may be ur required voltage i.e rated voltage on motor or machine when it is running on load

other wise u can check with grid supply or substation to get required voltage

Is This Answer Correct ?    4 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What is the drawback of class b amplifier? How is this minimized?

672


temp of cast resin 1500kva tx formerwent up to 138.c but came down very fast to about 100.c within 20 mins when load was reduced from 70% to 60%

1499


Can I use distributon class/transmission class Lightning arresots for protecting the building? If not why please explain?

1426


How to reduce the static electricity producing in solvent room? By P.D.Patil BioCon

1581


Why is the frequency not changed during transformation of electrical energy in a transformer?

853






Do you know what is dry-out test in x'mer

2218


Electromagnetic torque developed by the motor is compared to shaft torque. A less B same C depends on motor design D more

1557


how slip power recovery system work

2536


i want to model paper for section engg.

1571


How to check the LM324 Ic

8030


what is self capacitance of inductor

1841


sourse is 66 KV / 350 MVA, transfarmer is 1000 KVA 6.6 / 0.415 kv, iF fault is 28.75 MVA on 0.415 KV Bus then calculat the Transfarmer Impidance

1654


in Contactor opearation Why there is a difference in the values of the operate and release voltage in case AC supply

1574


What is the difference between shortcircuit current, rated current of cable & MCB with example? What will be the size of cable required for 5.5 KW motor (Full load current 10 Amps approx.), Starting current with DOL is 120 Amps. Aprrox. Short circuit current with LLLG fault is 2000 Amps Approx.

1588


-How do you select cable size for a given load at a given distance from source of supply. How do you find voltage drop.

1365