Will it be OK to connect a 5MVA 33/6.6kV Ynd11 Transformer
to a Star connected Motor. Or on other words connecting a
Delta to a Star.
I have another 30MVA 33/11 Dyn11 and would it be practical
to convert it to Dd0 consequently converting the Voltage
Ratio to 33/6.35kV Dd0.
Answer Posted / a.p.nanjappa
yes. what is the capacity of motor?
In your case , grid voltage is 33kv, Yn connected.Hence
power transformer has neutral connection brought
out.Neutral CT is installed to detect the ground faults.
secondary of 5MVA tranformer is 6.6kv,
This is Feeder bus voltage.6.6kv Feeder bus feeds Motor (
star connected). and Feeder bus is not interconnected to
another source. It is independent.This 6.6kv rotates at 30
lagging to primary3kv system.
Motor must be use inverse & instantaneous time
overcurrent and earth fault ( CDG61+cdg12) or equivalent
manufacturer protection
we use delt to star as weelas star 6.6motor.
No problems experienced.
In the othercase to change a 30MVA,33/6.35KV IS
REDESIGN/MANUFATURING. iT IS EXPENSIVE.No use at all and
advantage. You should change 6.6kv sw.gr also.
Is This Answer Correct ? | 1 Yes | 0 No |
Post New Answer View All Answers
Define availability (operational)?
some time we open engine breaker 8.0 MW load but plant not trip. and another time engine open 4.0 MW load engine trip why? individually engine breaker open & individually emergency stop why difference?
What are the advantages and disadvantages of negative feed back?
What are the factor to be consider for CT selection in 132kV substation?
What is the effect on 3phase induction motor if current setting knob of DOL kept at minimum current?
difference between Ac and Dc mcb ????
Ceiling Fan and Storage type water heater. Discuss
How will change the frequency in distribution side?
what questions will be asked for 11/33KV licence interview APSEB hyderabad. Can any one share question and answers.
current transformer balance the power level on both sides. e.g in case of step up, at secondary side voltage rise but current decrease and vice versa in case of step down transformer. but how this power level remains same in case of current transformer and voltage transformer
Is it possible to operate a synchronous 2-poles turbogenerator with a still-in-place faulted bar but electrically disconnected ???? If yes, should I act on the other phases as well ???
I completed iti in2004 I was worked in A grade contractor can I get c licence
what is the size of cable for 15kw motor and 85 meter cable length using with vfd
while doing high voltage test on 11kv/433 distribution transformer why we only give 28 kv on hv side and 3kv on lv side for power transformers what is the value what factors it depends
please suggest some good universities with low cost iam in totally full confusion so please help me my profile gre 283 and ielts 5.5