Why Boiler Drum level transmitter (TX) or level transmitter
rang always put -600 to 0 other -900 to 0. Mines range why
useā€¦.?

Answer Posted / radha

this is called wet leg system,so you are telling range -600
to 0 means your drum distance between HP & LP 600 mm and HP
and LP legs both are filled with condensate(water)
continueosly but LP leg distance higher than the HP leg,so
LP side pressure will acting 600mmWC extra, compare with HP
leg pressure,so we have to eliminate that pressure LP
pressure 600mmWC
thats why -600mmWC = 4mA
0 mmWC = 20mA

Is This Answer Correct ?    23 Yes 7 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

Which Signal hart communicator work? If there any signal change when hart connect while transmitter in line ?

930


control panel design guidelines

2860


How to convert mmWc(mili meter water colam) to tph(ton per hour)?

493


how to control pid

1457


Lux meter is the measuring device to measure the lux level of lighting fixture. in industrial sector two types of lighting fixture is being used as street lighting purpose 1. HPSV (Sodium) and 2. HPMV (Mercury). HPMV having white light which is an combination of red, blue and yellow colour, while HPSV haivng Yellow lighting. in HPSV red & blue colour will be absent. during measurement of the lux level of HPSV and HPMV fixture. 1. Lux meter can measure the actual lux level of both fixture? 2. or it will show false reading for HPSV fixture light as it has only yellow light present. please give me answer

4172






why we are using drum level control valve air to close?

1606


Define the terms Accuracy, precission, Spam, process tolerance while doing calibration of an instrument? Explaini with an example?

1566


how can we tune a PID. If it is by zeiger nichols method..please explain briefly with help of an example.

2015


can we create an interrupt in plc through scada?

1899


selection of the zener barrier for the hazardeous area zone 0

1775


what is installation and commissioning of (fat & sat) of power plant dcs ? this question keeps in desirable conditions of one company .

4404


For crude application in floating roof tank, how to calibrate a DP Transmitter? How is the floating roof weight considered?

2652


what is the criteria to decide conductor size of a cable ?

1286


Hi,can anyone help me out with PhD programs related to Instrumentation field?I have a degree in electronic Instrumentation?

1480


Which tank weighing system is better to install (Accuracy point of view) 1) Tank weighing system with 3 load cell or 2) Tank weighing system with 4 Load cell

743