how to choose the cable rating for load (KW)? EXAMPLE.50KW load

Answer Posted / mathhar

LOAD : 50kW , 415V , 0.8p.f
1- I = 28.75A
2- 28.75 * 1.2 = 34.5A
3- temp. factor * group factor = 0.75 "ex."
4- 34.5/.75 = 46A
5- choose 16mmsq
6- cal. Vd = (I * L(m) * delta(v)/ (V * 1000))*100%
its should less than 5%
7- short circuit temp. rise

Is This Answer Correct ?    19 Yes 17 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

wow to calculate the transformer rating(KVA)

1684


Hello to all, Please someone can send me HPCL ELECTRICAL Engg. Sample papers to me? Its urjent....my email address is.... raviasiapacific@gmail.com

1649


State the methods of improving power factor?

619


what is the formula of starting current of 3phase and 1 phase motor???

1726


I want single line diagram for AMF & DG syncronizing panel

6632






How to calculate cable size by using load.?? Any formula...

908


Igfet is a

1200


Can anybody tell abt concrete encased earthing or grounding?

1618


Earth bits close or open. Which is correct

1321


Dear all, I'm manikandan I have done by DIPLOMA EEE from 2011 , I have 5 years of experience from Power plant instrumentation field , which one field is give long life & which one field is best ,I confused a lot and also I'm studying AMIE, can I choose which department from Section B examination? pls tell me

1198


how to calculate insulation level of transformer?

1099


List some examples of renewable energy?

780


what is the minimum clearance between a 11KV 150KVAR capacitor cell and series reactor.can a series reactor can be mounted in the same structure of the capacitor cells structure

1737


What are electric motors?

658


How to calibrate or test an LT Air Circuit breaker 440 volts, 35 KA, 800 Amps ?

1512