what is procedure of calibration of remote seal
transmiter, botom to top flanch 850mm, fluid liquid
density .73, transmiter fixed on a fractionation colum,
under vaccume 10mbar

Answer Posted / aftab ahmed mazari

If you installed the remote seal transmitter at flanges,
then in case empty tank /vessel, the transmitter will
showing -mA. so do the followings:
1. Make transmitter 4 mA in this case(without any pressure,
only lower low leg remote seal pressure acting)
2. Apply 850 x 0.73 =620.5 mm of water to high side of
transmitter flange and set transmitter out put 20 mA.
aftabmazari@yahoo.com

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

what is the procedure of belt scale calibration?

1968


What is difference between radial vibration and axial vibration explain in detail .

1168


NPN transistor, SCR, Zener diode, LED, Varactor diode, Vortex meter, RTD, Resistor, Crystal

1742


WHAT IS MEANT BY PROJECT MANAGEMENT STRATEGIES IN INSTRUMENTATION?

3034


Define the terms Accuracy, precission, Spam, process tolerance while doing calibration of an instrument? Explaini with an example?

1564






What are the key features of a Distributed Control System? describing the various layers (sensor through to business system interfaces) as well as the hardware, software and security aspects of the DCS.

1796


how can leve transmetter calibate in feild .and also put cv and flow plz .....

1770


What is instrumentation technologists and mechanics?

575


Do you have reference list?

1423


Calibration procedure for electro magnetic flow meter

1536


god evening sir i am studying m.sc(tech)electronics &instrumention.am i elegible to all industies

1380


what is the responsibility of an instrument commissioning supervisor

2641


How is flow measured in square root?

680


Valve positioner and actuators in detail.

1385


what is the reset offset and control system in instrumentation

3114