hello dear
i have faced problem in drum level transmitter.
the problem is when i engrize the meter meter shows 100%
but the actual level 40 or something plz suggest me

Answer Posted / aftab ahmed mazari

It seems that transmitter low side leg is leaking, or low
side is not being fully condensing.
Please chck low leg fittings, connections and if ok. Then
check transmitter high side and low side pressures with the
help of digital pressure gauge. May be transmitter low side
any problem.When you calibrate tranmitter workshop, also
apply pressure to its low side, indication should go down
to confirm that low side is ok.

aftabmazari@yahoo.com

Is This Answer Correct ?    1 Yes 0 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

What are advantages and disadvantage of the ac supply load cell?

640


What are the application of bernoulli’s theorem?

686


If a control valve is hunting means means if we are giving 50% to the cv, the cv will open at 51% then slowly slwoly it will reaches 49% , so what to do for solve this problem. The cv is double acting and mounted for anti surge operation, it having 4 nos. volume booster, one sov, one positioner, etc..?

1633


Why grounding is necessary? Give example with diagram.

1755


What is the difference between modbus,fieldbus & profibus

1876






what is the procedure to callibrate temp controller ,pressure controller,etc. suppose a temp controller showing error 1.5 degree centigrate how can i minimize it.

1871


What is standard procedure of manual mapping in Radar type level transmitter?

1426


Explain how thw analog to digital converter works with the circuit diagram

2182


How does a single acting, spring return ball valve actually work? Does it require continuous air supply? 

1677


Good evening all I need a small favour regarding reliance paper i wanna probable sample papers(e&i) of reliance. if any of u have any idea about dis then plz mail me back.i belongs to electronics and instrumentation engg.so i need e&i papers. thanking u....

1653


flow transmeter accuracy 0.075% of full scale & find ucertainty is 0.025 % so what is maximum limit band of uncertainty

1832


Explain the combusion chamber

1578


my data card only does run in my mobile so how can change it that it run other mobile & computer and i can stor data in my data card

1823


how to tune siemens sipart electro pneumatic positioner..plz tel me..

1662


whats the abbreviation of IOP? is it instrument of power or input open problem?

666