how we can calculate which capacity capacitor bank we have
to add for improve pf?
Answer Posted / karuppiah
Let total power is 1500kw
assume
cos Q1 =power factor before improvement =0.75
cos Q2= poer factor after improvement =0.98
tan1=0.88{cos Q1=0.75,Cos-0.75=46.01degree,Now angle is
46.01,so tan(46.01)=0.88}
tan2=0.2
and
kvar 1= power*tan1=1500*0.88=1320kvar
kvar 2=power*tan2=1500*0.2=300kvar
now, required rating of capacitor bank =kvar1-kvar2
=1320-300
=1020kvar
Capacitor Bank should connect parallel with the load.
Thanks
Karups
Is This Answer Correct ? | 2 Yes | 1 No |
Post New Answer View All Answers
What do you mean by ratio correction factor of instrument transformer?
What will be the diameter of pipe between conservation tank and transformer
Briefly describe means used by electricity suppliers to influence the flow of active and reactive power in power networks (one for each type)?
What is excitation in case of dc motor?
how can motor both beasrings insulation resistance can be check?
What is the lower limit of break-down voltage of converter transformer.
how we start 40w tube light with 4 diodes,2capacitors,1 choke and without starter.(a product avilable in market which lights burnt tube lights also)
some time we open engine breaker 8.0 MW load but plant not trip. and another time engine open 4.0 MW load engine trip why? individually engine breaker open & individually emergency stop why difference?
what are the assumptions made in swineburne's test?
Explain how you can give the overload setting to any Motor Protection Relay for a HT motors with formula and example?
Q: How to calculate Transformer losses , tell us by Formula.
The electromagnetic torque developed is proportional to what in a D.C series motor?
Who are the manufactures those manufacturing 3Cx2.5sqmm FRLS cables. I heard about FRLS technology adopted only in wires useful for wirings
If SFU is Switch Fuse Unit, What is the expansion for FSHF in Electrical Engineering?
in a simple IDMT relay we use neutral point of ct for earth fault then what is the requirement of neutral ct and cbct?