What is the formula to find out cross sectional area of
cable for certain current rating?

Answer Posted / tarun aggarwal ymca

what u have to first take into mind what type of cable u want to purchase....then its size matter

usually we use XLPE insulated cable for Power cable and Aluminum or copper its depend upon the cost and loses

mean if u need large length cable you have to prefer aluminum in shorter length copper cable is preferred as its resistivity is less

for example

VLL = 11kV (line volatge)
L = 1.3km
Maximum allowable Vdrop = 2.5% of VLL i.e.Vdrop = 275V

SkVA = 3000kVA (Total Power we have to transfer of to be used by the connected load)
Full load Current If= SkVA/root3 VLL i.e If = 157.5A

Demand factor is what we actually demand the current (it not always full load current what we demand) Let D.F = 80% of If

Id =D.F x If (Demand Current) where D.F = Demand Factor i.e Id = 126.0A

The cable current carrying capacity is always kept larger than the demand current let S.F for Cable in % = 30% Extra Id

Ic= (1+S.F/100) Id i.e Ic = 163.8A

This current is what will be safer current that will be carried out by cable

Now derating factor K is calculated by the following equation

K = Kground x Ktherm.res x Kdepth x Kgroup

Vdrop = 3IdL root(Rac cos􀄳+ Xsin􀄳)

Now cable data is refered

Type 3 Core, Copper Conductor, XLPE insulated, Copper tape Screened, PVC bedded, Steel Wire Armoured, PVC, 8750/15000V.


Parameter -------- 50 mm2---- 70 mm2 ------ 95 mm2------- 120 mm2 ------- 150 mm2 ----- 185 mm2
Irated (A) --------- 187----------- 227- ------------ 267--------------303 -----------------338------------------ 383
Kground----------------0.86
Ktherm.res-- ----------- 1
Kdepth-------------------0.98
Kgroup ------------------0.7
K-------------------------- 0.590
Icor (A) -----------110.32 --------- 133.92----------157.52--------- 178.76-------------199.41------------225…
Rac (ohm/km) --- 0.493 --------0.342------------ 0.247------------0.196---------------0.1… ------------ 0.128
X (ohm/km) --------0.118 --------0.112 ------------0.106------------0.102------…
P.F = Cos--------0.85
(In radian)-------- 0.5548------ 0.5548----------0.5548-----------0.5548-…
Vdrop (V)-----------196.76-------167.73-------…

Considering the values of Ic, Icorrected and Vdrop the best suited cable is 120 mm2
cable for connecting switchyard to substation

Sorry extra long answer but i want to explain in detail

Is This Answer Correct ?    7 Yes 2 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

why using transformer and thyristor switch in 3 phase apfc panel

2380


What are the two basic types of transformers?

625


What do you mean by cogeneration? What its working principle?

2766


what are the components in electrical control panel (for example: 415V, 3-ph, panel to operate utility and 3-ph DG set).

1561


what is rocking arrangement in arc heating

1685






What is negative sequence over voltage element?

1429


What is the direction of current flow in ct secondary...means if the current is flowing from P1 to P2 then what will be the direction of current flow in ct secondaryw

1415


State kirchoff voltage law?

689


hwat type of motor is used in thermal gas turbine hydro nuclear power plants and why

1468


Hi Suppose we have a wye/wye transformer which is grounded at both sides,in this situation, do we have ay ground transformer? in other words, ground transformer can do any thing more (while we have nuetral wire in both sides)? As the last question, what about 3rd harmonic? we have two choices: first using wye/delta transformer + ground transformer and second using wye/wye earthed connection.in the former choice, we dont have 3rd harmoonic at the secondary side but what about Yn/yn conection? do we suffer from 3rd harmonic in the Yn/yn connection?

1527


What will be the voltage impact on secondary side of two transformers with different vector groups when both voltages are compared.

1519


how to read idmt curva

1716


is it possible for different brand of H.V transformers to run or operate in parallel to each other? if so how much disturbance can this affact the H.V bus bar?

1649


how to revers the direction of single phase motor

478


How to calculate capacitor bank size at a load 800kVA.

1173