How can one improve linearity of an RTD based temperature
measurement system?
Answer Posted / guest
RTD has +/- 0.4% nonlinearity when used over 0 to 200 degC.
This is due to the relationship R= R0*(1+aT+bT^2). The
change in resistance for 0 to 100 degC is 38.5ohms for a
Pt100, while it is lesser at 37.3 ohms fro 100 to 200 degC.
Using a two slope method, one for 0 to 100 deg and another
for 100 to 200 degC, the linearity error can be brought
down from +/- 4% to +/- 0.1%.
Is This Answer Correct ? | 5 Yes | 3 No |
Post New Answer View All Answers
Q- What are the application in which PNP transistor is preferred over NPN ?
What is wet leg condition and why is it used?
What are the types of valves?
what is wave length were using ?
What is Erosion in a control valve?
anybody having Qatar Petroleum questions for instrument Technician offshore ....please send me
How can you add value to this Industry if offered the job?
What is frequency factor in massflow meter? When using frequency output?
can anyone can let me know in Eurotron Micro cal 2+ calibrator in milli amps source mode we are not able to get 20 milli amps output it only produces 1.52 milli amps out, but display shows increase in milli amps , and err6 displays, let me know how to remove the err 6.
god evening sir i am studying m.sc(tech)electronics &instrumention.am i elegible to all industies
How can test or measure the probe and extension cable to identify if the problem at the probe or cable or at the driver it self? (pleast notify the measuring method)
Whatis the reset ofset and control system in instrumentation
What is instrumentation measurement?
please send me the inteview questions in IOCL
Working principle of magnetic flow meter ......and calibration procedure of e+h magnetic flowmeter...